Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.

HORIZONTAL SIDEWALL VENTING

For applications where vertical venting is not possible, the
only approved method of horizontal venting is the use of an
auxiliary power vent. Auxilary power venters must be
approved by CSA, UL, or other recognized safety agencies.
Follow all application and installation details provided by the
manufacturer of the power vent.

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters.

All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.

NOTE: Single side return above 1800 CFM is approved as
long as the filter velocity does not exceed filter manufac-
turer’s recommendation and a transition is used to allow use
of a 20x25 filter.

LEFT SIDE

RIGHT SIDE

.5”

.5”

RETURN END

B

24.25”

29.5”

28.5”

Electrical
Entry

Gas Pipe
Entry

Thermostat
Wiring

FRONT

14”

1”

1.5”

23”

SUPPLY END

C

24.38”

20”

.5”

B

Gas Pipe
Entry

Thermostat
Wiring

33”

A

.5”

Electrical
Entry

Vent Connection
Outlet

Vent
Connection
Outlet

4” Diameter

Outlet

Vent Connection

Cabinet and Duct Dimensions

Models

Nominal

CFM (m

3

/min)

Cabinet

Size

Cabinet Dimensions (Inches)

Approximate

Operating Weights

A

B

C

Lbs

TM(8,L)X060A12MP11

1200

A

14 1/2

13 3/8

10.3

94

TM(8,L)X080B12MP11

1200

B

17 1/2

16 3/8

11.8

103

TM(8,L)X080C16MP11

1600

C

21

19 7/8

13.6

114

TM(8,L)X100C16MP11

1600

C

21

19 7/8

13.6

118

TM(8,L)X100C20MP11

2000

C

21

19 7/8

13.6

122

TM(8,L)X120C20MP11

2000

C

21

19 7/8

15.8

129

Ratings & Physical / Electrical Data

Models

Input

Output

AFUE

Air Temp.

Rise

Max. Outlet

Air Temp

Blower

Blower

Size

Max

Over-Current

Protect

Total Unit

Amps

Min. wire Size

(awg) @ 75 ft

one way

MBH

MBH

°F

°F

HP

Amps

TM(8,L)X060A12MP11

60

48

80.0

30-60

160

1/2

6.8

11 x 8

15

9.3

14

TM(8,L)X080B12MP11

80

64

80.0

35-65

165

1/2

6.8

11 x 8

15

9.3

14

TM(8,L)X080C16MP11

80

64

80.0

25-55

155

1/2

6.8

11 x 10

15

9.3

14

TM(8,L)X100C16MP11

100

80

80.0

35-65

165

1/2

6.8

11 x 10

15

9.3

14

TM(8,L)X100C20MP11

100

80

80.0

25-55

155

3/4

8.4

11 x 11

15

10.9

14

TM(8,L)X120C20MP11

120

96

80.0

35-65

165

3/4

8.4

11 x 11

15

10.9

14