Fan Performance — 50PG14 Horizontal Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3750

542

0.93

607

1.10

665

1.27

719

1.44

770

1.62

3950

564

1.07

626

1.25

683

1.43

735

1.61

785

1.79

4150

586

1.22

645

1.41

701

1.60

752

1.78

800

1.97

4350

608

1.38

665

1.58

719

1.78

769

1.98

816

2.17

4550

630

1.55

685

1.77

737

1.98

786

2.18

832

2.39

4750

652

1.75

705

1.97

756

2.19

804

2.40

849

2.62

4950

674

1.95

726

2.19

775

2.42

822

2.64

866

2.86

5150

697

2.18

747

2.42

794

2.66

840

2.89

883

3.13

5350

719

2.42

767

2.67

814

2.92

858

3.16

901

3.41

5550

742

2.67

789

2.94

834

3.20

877

3.45

918

3.70

5750

765

2.95

810

3.22

854

3.49

896

3.76

936

4.02

5950

788

3.24

831

3.53

874

3.81

915

4.08

955

4.36

6150

811

3.56

853

3.85

894

4.14

935

4.43

973

4.71

6250

822

3.72

864

4.02

905

4.32

944

4.61

983

4.89

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3750

 818

1.79

 865

1.97

 909

2.16

 952

2.35

 994

2.54

3950

 832

1.97

 877

2.16

 920

2.35

 963

2.55

1003

2.75

4150

 846

2.16

 890

2.36

 932

2.56

 974

2.76

1014

2.97

4350

 861

2.37

 904

2.57

 945

2.78

 985

2.99

1024

3.20

4550

 876

2.59

 918

2.80

 959

3.02

 998

3.23

1036

3.45

4750

 892

2.83

 933

3.05

 973

3.27

1011

3.49

1049

3.72

4950

 908

3.09

 948

3.31

 987

3.54

1025

3.77

1061

4.00

5150

 924

3.36

 964

3.59

1002

3.83

1039

4.06

1075

4.30

5350

 941

3.65

 980

3.89

1017

4.13

1054

4.38

1089

4.62

5550

 958

3.96

 996

4.21

1033

4.46

1069

4.71

1103

4.96

5750

 975

4.28

1013

4.54

1049

4.80

1084

5.06

5950

 993

4.63

1030

4.89

1065

5.16

6150

1011

4.99

6250

1020

5.18

LEGEND
Bhp -
Brake Horsepower

High Range Motor/Drive Required

NOTES:

1. Motor drive range is 690 to 893 for low range motor/drive and 852 to 1055 rpm for
high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 3.70 for low range motor/drive and 5.25 for high range
motor/drive.
3. See General Fan Performance Notes.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1. Static pressure losses from accessories and options

(Humidi-MiZer

 system, economizer, etc.) must be added

to external static pressure before entering Fan Performance
table. Refer to Accessory/FIOP Static Pressure information.

2. Interpolation is permissible. Do not extrapolate.

3. Fan performance tables are based on wet coils, clean filters,

and casing losses. Gas heat losses are included for 48 series
units.

4. Extensive motor and drive testing on these units ensures

that the full horsepower range of the motor can be utilized
with confidence. Using the fan motors up to the bhp rating
shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.

5. Use of a field-supplied motor may affect wire size.

Recalculate the unit power supply MCA and MOCP if
required. Contact your Carrier representative for details.

6. Use the following formula to calculate input watts:

Input Watts = Bhp x (746/Motor Eff)

48/50PG and PM