Beckett 61847 Combination Control User Manual

Genisys, Combination control r8182h replacement kit, Installation instructions

Advertising
background image

52199 AquaSmart

®

/ GeniSys

®

Combination Control

R8182H Replacement Kit

Installation Instructions

This control package is intended to replace the Honeywell R8182H triple acting Aquastat

®*

. Please read the supplied

literature for the GeniSys burner control (61649) and AquaSmart boiler control (61738) before beginning the installation.

1. Make sure power is turned off to the heating system.
2. Record all R8182H temperature limit and differential

settings for reference.

3. Remove and mark all wires terminated in the old

control.

4. Remove necessary conduit from the boiler control.
5. Carefully remove the boiler control from the immersion

well.

6. Inspect and clean the immersion well, preparing it for

the installation of the AquaSmart temperature sensor.
(See AquaSmart literature (61738) for details)

7. Mount the AquaSmart control to the immersion well,

per instructions outlined in the AquaSmart Manual.

8. Mount the 4x4 box extension with the burner control to

the 4x4 box on the oil burner, or to an accessible 4x4
box near the appliance.

9. Wire the unit as appropriate for your system

requirements. See the available options in the
enclosed AquaSmart literature pages 12-24 and
GeniSys literature for burner component wiring.

10. Turn power on. Program AquaSmart to desired

temperature and differential settings.

11. Observe a complete call for heat cycle to ensure the

control performs all programmed functions and shuts
off at set temperature.

INCLUDED PARTS:

(1) AquaSmart Control, Part No. 7600A001

(1) GeniSys Control, Part No. 7505A0000

(1) Wire Harness 1, Part No. 52193 (5 wire)

(1) Wire Harness 2, Part No. 52194 (4 wire)

(1) 4x4 Box Extension, Part No. 32778

(1) 48” Sensor Extension, Part No. 5212001

Explosion, Electric Shock,
Burn and Scald Hazards

Excessive water temperatures could cause

explosion, burns, scalding, pressure relief

fl ooding and fi tting leaks.

For proper installation, follow the steps outlined below.

Part No. 61847 R01, Printed in the USA

02/12

R.W.

BECKETT

CORPORATION

P.O. Box 1289, Elyria, Ohio 44036

R.W. BECKETT CANADA, LTD

430 Laird, Unit 3, Guelph, Ontario, N1G 3X7

All necessary wires labeled and

located under the 4x4 box extention

*Aquastat is a registered trademark of Honeywell International, Inc.