P5-m32t-e5src – Cooper Lighting E5SR User Manual

Page 2

Advertising
background image

P H O T O M E T R I C S

P5-M32T-E5SRC

Test No.

H36117

Lamp:

26W PLT

Lumens:

1800

Cutoff:

75°

Spacing:

1.1

Efficiency:

32.4%

Unit LPW:

22.43

Unit Number: P N 5 - M 3 2 T- E 5 S R C

C a n d e l a s

Vertical

CD

Angle

90

0

85

0

75

5

65

37

55

82

45

142

35

202

25

256

15

294

5

309

0

311

L u m i n a n c e

Degree

cd/m

2

85

˚

0

75

˚

1410

65

˚

6266

55

˚

10183

45

˚

14384

4'6"

5'6"

6'6"

8'0"

10'0"

12'0"

5'0"

6'6"

7'6"

9'6"

11'6"

14'0"

15

10

7

5

3

2

C o n e o f L i g h t

Distance to

Initial Nadir

Beam

Illuminated Plane

Footcandles

Diameter

Notes and Formulas:

Luminance: To convert cd/m

2

to footlamberts, multiply by 0.2919

Cone of Light:
• Footcandle and CU multiplier: clear x 1.0, Haze x .95, Gold x .90, Black x .65, Warm Haze x .90
• Beam diameter is to 50% of maximum footcandles, rounded to the nearest half-foot.
• Footcandle values are initial. Apply appropriate light loss factors where necessary.

CU Notes/Formulas:
• maintained illuminance=lamp lumens x CU x light loss factors

room area

• total number of luminaires=total room area x maintained illuminance

lamp lumens x CU x light loss factors

• CU data based on 20% effective floor cavity reflectance.

80%

70%

50%

30%

0%

70

50

30

10

50

10

50

10

50

10

0

38

38

38

38

38

38

36

36

34

34

32

36

35

34

33

34

33

33

32

32

31

29

34

32

31

29

32

29

30

28

29

28

26

32

29

27

26

32

29

30

28

29

28

26

30

27

25

23

26

23

26

22

25

22

21

28

24

22

20

24

20

23

20

23

20

19

26

22

20

18

22

18

21

18

21

18

17

24

20

18

16

20

16

19

16

19

16

15

22

18

16

14

18

14

18

14

17

14

14

21

17

15

13

17

13

16

13

16

13

12

19

16

13

12

15

12

15

12

15

12

11

Ceiling Reflectance

Wall Reflectance

Room Cavity Ratio

0

1

2

3

4

5

6

7

8

9

10

C o e f f i c i e n t o f U t i l i z a t i o n

Z o n a l L u m e n S u m m a r y

Zone

Lumens

%Lamp

%Luminaire

0-30

230

12.8

39.5

0-40

356

19.8

61.1

0-60

539

30.0

92.6

0-90

582

32.4

100.0

90-180

0

0.0

0.0

0-180

582

32.4

100.0

D i s t r i b u t i o n

Note: Specifications and Dimensions subject to change without notice.

Visit our web site at www.cooperlighting.com

Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 486.4801 ADI030825

Cooper Lighting 5925 McLaughlin Rd. Mississauga, Ontario, Canada L5R 1B8 905.507.4000 FAX 905.568.7049

Advertising