Applicable to models: cfd-1r, cfd-2r, cfd-3r, Coldtech® refrigerator settings – ColdTech CFD-2F User Manual

Page 9

Advertising
background image

ColdTech® Refrigerator Settings

Temperature set to 37 F

Parameter Function

Set Range

Default

E1

Lower Setpoint Limit

-40 F ~ set temp

36 F

E2

Higher Setpoint Limit

set temp ~ 120 F

45 F

E3

Hysteresis, temp. variance

1 ~ 18 F

10 F

E4

Comp. start delay time

0 ~ 10 min.

2 min.

E5

Offset on room temp

-5 ~ 5 F

0 F

E6

Offset on evap temp

-5 ~ 5 F

0 F

F1

Max. defrost duration

1 ~ 60 min.

N/A

F2

Defrost interval time

0 ~ 24 hr.

0

F3

Defrost termination temp

32 ~ 68 F

N/A

Key

F = Farenheit (degrees)

temp = temperature

min. = minutes

max = maximum

hr. = hours

N/A = not applicable

Warning:

Do not change the default settings of your ColdTech unit

without consulting a qualified service technician or the

ColdTech service department.

-9-