Venting System: The furnace flue pipe, vent connector, barometric damper, and
chimney should be inspected for:

• Signs of excessive rust, corrosion pitting, and holes.

• Signs of condensation or moisture leakage (sometimes indicated by soot or

condensate streaks).

• Evidence of structural damage, and loose or disconnected piping joints.

• Presence animal nests.

• Free movement of the vane of the barometric damper without binding or

interference.


If any problems are evident, call a qualified heating contractor for assistance.

NOTICE: A qualified heating contractor MUST service the oil burner and inspect
the heat exchanger in this furnace at least once a year.