Warning, Caution – Carrier 58PHA/PHX User Manual

Page 36

Advertising
background image

36

START--UP, ADJUSTMENT, AND SAFETY

CHECK

General

FIRE HAZARD
Failure to follow this warning could result in personal

injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in

the gas control area. The switches open and shut off power

to the gas valve if a flame rollout or overheating condition

occurs in the gas control area. DO NOT bypass the

switches. Correct inadequate combustion air supply

problem before resetting the switches.

!

WARNING

CUT HAZARD
Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses and

gloves when handling parts and servicing furnaces.

CAUTION

!

1. Maintain 115--v wiring and ground. Improper polarity will

result in rapid flashing LED and no furnace operation.

2. Make thermostat wire connections at the 24--v terminal

block on the furnace control. Failure to make proper

connections will result in improper operation. (See Fig.
25.)

3. Gas supply pressure to the furnace must be greater than

4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5

psig).

4. Check all manual--reset switches for continuity.
5. Install blower compartment door. Door must be in place to

operate furnace.

6. Replace outer door.

Start--Up Procedures

FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury,

death and/or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections.

!

WARNING

1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
3. To Begin Component Self--Test:

Remove blower access door. Disconnect the thermostat R
lead from the furnace control board. Manually close the

blower door switch closed. Short (jumper) the COM--24v
terminal on control to the TEST/TWIN 3/16--inch quick
connect terminal on control until LED goes out

(approximately 2 sec). Gas valve and humidifier will not
be turned on. (See Fig. 24.)

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury, or death.
Blower access door switch opens 115--v power to control.

No component operation can occur unless switch is closed.

Caution must be taken when manually closing this switch

for service purposes.

!

WARNING

NOTE: The furnace control allows all components, except the
gas valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Component test sequence is as follows:
Refer to service label attached to furnace or see Fig. 55.

a. LED will display previous status code 4 times.

b. Inducer motor starts and continues to run until Step f of

component test sequence.

c. Hot surface igniter is energized for 15 sec., then off.

d. Blower motor operates on HEAT speed for 10 sec.

e. Blower motor operates on COOL speed for 10 sec.

f. Inducer motor stops.

g. Reconnect R lead to furnace control board, release blower

door switch and re--install blower door.

4. Operate furnace per instruction on door.
5. Verify furnace shut down by lowering thermostat setting

below room temperature.

6. Verify furnace restarts by raising thermostat setting above

room temperature.

Adjustments

FIRE HAZARD
Failure to follow this warning could result in injury, death

and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.

This can result in unregulated manifold pressure and result in

excess overfire and heat exchanger failures.

!

WARNING

FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace

life.
DO NOT redrill orifices. Improper drilling (burrs,

out--of--round holes, etc.) can cause excessive burner noise

and misdirection of burner flames. This can result in flame

impingement of heat exchangers, causing failures. (See Fig.

53.)

CAUTION

!

Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft. (610 M). Furnace input rate must be

within +/--2 percent of furnace rating plate input. For altitudes

above 5500 ft. (1676 M), a field--supplied high altitude pressure
switch is required.

1. Determine the correct gas input rate.

In the U.S.A.:

58PH

A

Advertising