Appendix : Lightning Proof and Surge Signal Proof

The product adopts TVS lightning proof technology to prevent from damage by lightning
strike below 1500 W and impulse signals such as surge; but it is also necessary to abide
by the following precautions to ensure electrical safety based on practical circumstances:

Keep the communication cables at least 50 meters away from high voltage
equipment or cables.

Make outdoor cable laying-out under eaves as possible as you can.

In open area shield cables in steel tube and conduct a single point ground to the tube.

Trolley wire is forbidden in such circumstances.

In strong thunderstorm or high faradic zone (such as high voltage transformer

substation), extra strong lightning proof equipment must be installed.

Take the building lightning proof requirements into account to design the lightning

proof and grounding of outdoor equipment and cable laying-out in accordance with
the national and industrial standards.

The system must be grounded with equal potentials. The earth ground connection

must satisfy the anti-interference and electrical safety requirements and must not
short circuited with high voltage electricity net. When the system is grounded
separately, the resistance of down conductor should be ≤ 4Ω and the sectional area
of down conductor should be ≤25mm2 (refer to Figure I).