Maintenance – Chromalox V-2020 User Manual

Page 2

Advertising
background image

2150 N. RULON WHITE BLVD., OGDEN, UT 84404

Phone: 1-800-368-2493 www.chromalox.com

MOUNTING

WIRING

OPERATION

RENEWAL PARTS IDENTIFICATION

WARNING: Hazard of Shock. Any installation involving
electric heaters must be effectively grounded in accor-
dance with the National Electrical Code to eliminate
shock hazard.
Note: All wiring should be done in accordance with local codes and the

National Electrical Code by a qualified person as defined in the NEC.
1. Electrical wiring enters heater case through 7/8” opening in end of

heater.

2. Grounding conductor, with green insulation, should be secured to

grounding screw located on case.

Width

Height

5-3/4

3/4

Dimensions (In.)

Model

Height

Width

Depth

V-2020

27

12-3/4

5-3/4

V-2030

27

12-3/4

5-3/4

V-2040

27

17-3/4

5-3/4

Heater Mounting —

4 or 6 Elements

L1

L2

Line 240V

4 or 6 Elements

L1

L2

Line 480V

WARNING: Hazard of fire or discoloration of temperature
sensitive fabrics. Keep combustible materials and such
fabrics at least 4” away from front of cover or above cover.
DANGER:Hazard of Fire. This heater is not intended for

use in hazardous atmospheres where flammable vapors,
gases, liquids or other combustible atmospheres are pre-
sent as defined in the National Electrical Code. Failure to
comply can result in explosion or fire.

MAINTENANCE

1. WARNING: Hazard of Shock. Disconnect all power

before attempting to service this heater.

2. Following long periods of idleness, heater should be vacuumed

before start-up to remove accumulated combustible particles which
will incinerate causing smoking and consequent wall discoloration.

3. If heater is located in areas of heavy traffic, furnish suitable heater

guard (wall mounted pipe rail in front of case, for example) to pre-
vent damage to heater.

Figure 1 — 240 Volt Heaters

Figure 2 — 480 Volt Heaters

1

2

3

4

Type V

Heating Element

Heater

Insulating

Insulating

Wire

Wiring

(Iron Sheath)

Cover

Bushing

Bushing

Sizes

Diagram

Model

Volts Watts

(Prefix 152-)

(Prefix 032-)

(Prefix 032-)

(90˚C Min)

Fig No.

V-2020

240

2000

SE-2450 240V 500W (4)

108259-001

010978-001 (8)

010978-002 (8)

#16

1

V-2030

240

3000

SE-2475 240V 750W (4)

108259-001

010978-001 (8)

010978-002 (8)

#16

1

V-2030

480

3000

SE-2475 240V 750W (4)

108259-001

010978-001 (8)

010978-002 (8)

#16

2

V-2040

240

4500

SE-2475 240V 750W (6)

108259-002

010978-001 (12) 010978-002 (12)

#14

1

V-2040

480

4500

SE-2475 240V 750W (6)

108259-002

010978-001 (12) 010978-002 (12)

#16

2

Limited Warranty:

Please refer to the Chromalox limited warranty applicable to this product at

http://www.chromalox.com/customer-service/policies/termsofsale.aspx.

Advertising
This manual is related to the following products: