1 Overview

The EN1212/EN1212-60 universal dual input transmitter it designed to be
used with any standard contact or sensor. Inovonics mult-function add-on
receivers will support both inputs as separate devices.

Note: The universal dual input transmitter requires use of a serial receiver
or network coordinator, as well as an application designed to support
advanced functionality.

Note: For UL 2560 installations, refer to the EN6080 Area Control
Gateway Installation Instructions
.

1.1 Maximum Number of Repeaters for a UL2560 Installation

To achieve the 99.99% alarm message reliability required for UL2560
compliance, system installations must operate within the following limits
for end device and repeater counts.

1.2 Inovonics Wireless Contact Information

If you have any problems with this procedure, contact Inovonics Wireless
technical services:

E-mail: [email protected].

Phone: (800) 782-2709.

1.3 Universal Dual Input Transmitter Components

Figure 1 Universal dual input transmitter components

1.4 What’s In The Carton

Three wall mount screws.

Three wall mount anchors.

Two selection jumpers.

One 3.0V lithium battery.

2 Installation and Startup

2.1 Installation Notes

These products are designed to be installed and maintained by
professional security technicians.

Products are intended for indoor use.

Manually test all products weekly.

2.2 Install/Replace the Battery

1.

Pry the top lip of the mounting bracket up, and lift the bracket off of the
transmitter.

2.

Use your thumb to depress the housing release tab on the bottom of
the transmitter; separate the housing.

3.

If replacing a battery, use the hole in the back of the housing to push
the old battery out of the battery holder.

4.

Install the new battery.

5.

Press the reset button to initialize the transmitter.

2.3 Select the Frequency Band

EchoStream products are able to use a range of radio frequencies, and
must be configured for your geographic area. This product ships with a
default frequency range of 902-928 MHz for use in North America. If you
are using the product in North America, skip to section 3, “Connect Input
Wiring”; if you are using the product in Australia or New Zealand, you will
need to configure the transmitter.

6.

Place a selection jumper on the appropriate frequency band selection
pins.

Place the jumper on the right two pins, marked NZ, to set the
frequency range to 921-928 MHz for New Zealand.

Place the jumper on the left two pins, marked AU, to set the
frequency range to 915-928 MHz for Australia.

7.

Press the reset button to complete configuration.

Caution: When pressing the reset button, make sure you don’t also touch
the frequency band selection pins. Touching the frequency band selection
pins while pressing the reset button can inadvertently set the single input
universal transmitter to the wrong frequency band.

3 Connect Input Wiring

The transmitter has a three-terminal contact block that can connect inputs
from one or two external contact loops. The middle terminal is a ground,
which is shared by both contact loops. Input one can be configured for
either a normally open or a normally closed contact loop using the NO/NC
selection pins; input two is always normally closed.

8.

Connect wiring for the inputs you will be using.

9.

If you are not using input two, connect wiring between the input
terminal terminal and the ground terminal to set it for normally closed.

4 Select Input Type

The N/O-N/C selection pins allow the choice of a normally open or
normally closed state for the contact circuit wired to the input one terminal.

The terminal is shipped set for normally closed, with no selection jumper
on the N/O selections pins.

10. Place a selection jumper on the selection pins to select normally

open; remove the selection jumper from the selection pins to select
normally closed.

11. Press the reset button to complete configuration.

4.1 Register the Universal Dual Input Transmitter

Transmitters must be registered with the system in order to be monitored
and supervised. When supervised, the transmitter will send a check-in
message to the receiver. EN1212 transmitters send a check-in message
every three minutes; EN1212-60 transmitters send a check-in message
every 60 minutes. Each transmitter has a unique factory-programmed
identification number.

Note: For UL 2560 installations, transmitters must have a minimum
check-in time of 60 minutes.

Refer to the receiver installation instructions for details on registering a
transmitter.

12. When prompted by the receiver to reset transmitter, press the reset

button.

13. Replace the cover.

Caution: The universal dual input transmitter should be tested after
registration to ensure operation. To test the universal dual input
transmitter, activate each of the conditions and ensure an appropriate
response.

4.2 Mount the Universal Dual Input Transmitter

14. Mount the bracket on the wall with the screws provided.

15. Clip the transmitter onto the bracket. Hook the bottom catch first, then

press the top into place.

16. The housing may be secured with a third mounting screw, located

beneath the battery.

Note: Accessing this screw on an active transmitter requires opening the
housing and removing the battery, causing a tamper condition.

17. To dismount the universal dual input transmitter, pull the transmitter

housing carefully out of the mounting bracket from the top.

5 US Patent Numbers

7,154,866.

7,554,932.

7,746,804.

Other patents pending.

End Devices

Maximum
Repeaters

150

397

250

386

350

375

500

360

1000

313

2000

238

3000

184

A Tamper button and spring

B NO/NC selection pins

C Input one terminal

D Ground terminal

E Input two terminal

F Reset button

G Frequency band selection pins

A

B

C

G

F

E

D