Inovonics EN1242 User Manual

Page 2

Advertising
background image

10.17.12 05362H © Inovonics, 2012 - www.inovonics.com

2

2.4 Select the Frequency Band

EchoStream products are able to use a range of radio frequencies, and
must be configured for your geographic area. This product ships with a
default frequency range of 902-928 MHz for use in North America. If you
are using the product in North America, skip to 2.5, “Set CleanMe®/Low
Battery Reporting”; if you are using the product in Australia or New
Zealand, you will need to configure the transmitter.
7. Place a selection jumper on the frequency band selection pins

appropriate to your geographic area.

• Place the jumper on the right two pins, marked NZ, to set the

frequency range to 921-928 MHz for New Zealand

• Place the jumper on the left two pins, marked AUS, to set the

frequency range to 915-928 MHz for Australia.

8. Press the reset button to complete configuration.

Caution: When pressing the reset button, make sure you don’t also touch
the frequency band selection pins. Touching the frequency band selection
pins while pressing the reset button can inadvertently set the device to the
wrong frequency band.

2.5 Set CleanMe

®

/Low Battery Reporting

Set as the factory default, the EN1242 combines the low battery signal with
a signal indicating the detector needs cleaning. If you want to use this
multiple condition indication, skip to 2.6, “Register the EN1242”. If multiple-
condition indication is not desired, you can disable wireless reporting of the
CleanMe status.
9. To disable CleanMe reporting, move the jumper on the low battery/

CleanMe selection pins to Low Bat.

Note: Low battery/CleanMe messages are suppressed when an alarm is
being transmitted.

Note: Even if CleanMe notification is disabled, the sensitivity test will still
indicate sensor condition.

2.6 Register the EN1242

The EN1242 must be registered to function in your EchoStream system.
Refer to your receiver, network coordinator or control panel manual for
registration instructions. Inovonics Wireless recommends all EchoStream
transmitters be supervised.
10. When prompted, press the EN1242 reset button to complete

registration.

2.7 Mount the EN1242

11. Use the provided anchors and screws to mount the EN1242, paying

careful consideration to the following best practices:

Caution: Regulations pertaining to smoke sensor installations vary. For
more information, contact your local fire department or local authority
having jurisdiction.

• Install a minimum of two smoke sensors in any household.
• Put a smoke sensor in the hallway outside of every bedroom area.
• Put a smoke sensor on every level of a multi-level residence.
• In rooms with sloped ceilings, install smoke sensors 0.9m (3 feet)

measured down from the highest point of the ceiling.

• Install basement sensors on the ceiling as close to the center of the

room as possible. If this is not practical, install on the ceiling no closer
than 10cm (4 inches) from any wall or corner.

• If ceiling mounting is not practical, install on an inside wall between 10

an 15cm (4 and 6 inches) from the ceiling.

• Put smoke sensors at both ends of a bedroom hallway if the hallway is

more than 9m (30 feet) long. Large rooms over 84 square meters (900
square feet) require more than a single sensor.

• Areas with rough ceilings or short, transom-type walls coming down

from the ceiling require additional smoke sensors.

• Install second-floor smoke sensors on the ceiling at the top of the first-

to-second floor stairwell. Be sure that no door or other obstruction
blocks the path of smoke to the sensor.

Do not locate sensors:

• To a drop ceiling tile; mount it to a metal runner.
• In or near areas such as kitchens or garages, where smoke or vehicle

exhausts normally occur (protect these areas with heat-detection
devices, not with smoke sensors); near furnaces, hot water heaters,
or gas space heaters.

• In damp or very humid areas, or next to bathrooms with showers.

Install sensors at least 1.5m (5 feet) away from bathrooms.

• In very cold or very hot areas.
• In dusty, dirty, or insect infested areas.
• Near fresh air inlets or returns or excessively drafty areas. Air

conditioners, heater, fans, and fresh air intakes and returns can drive
smoke away from smoke sensors.

• In dead air spaces at the top of a peaked ceiling or wall/ ceiling

intersect. Dead air may prevent smoke from reaching a smoke sensor.

• Near fluorescent light fixtures. Install smoke sensors at least 3m (10

feet) away from fluorescent light fixtures.

• Between protruding ceiling structures such as beams or walls which

can create dead air spaces and may prohibit smoke from reaching the
detector.

Caution: All sensors are subject to possible compromise or failure-to-warn
for a variety of reasons. For example: Smoke sensors cannot detect smoke
in chimneys, walls, roofs, or smoke blocked by a closed door; sensors may
not detect smoke on other levels of the building; sensors may not warn in
time when fires are caused by smoking in bed, explosions, improper
storage of flammables, overloaded electrical circuits, or other hazardous
conditions.

3 Test the EN1242

Caution: To avoid a fire department dispatch, contact the central
monitoring station or, if possible, put the system into sensor test mode.

There are two ways to test the EN1242 smoke detector sensor. The
sensitivity test should be performed every week; the smoke test should be
performed at least once a year. Both tests activate the alarm sounder and
send alarm signals.
The EN1242 should also be tested after initial registration, as well as each
time the smoke chamber is changed or the batteries are replaced.

3.1 Smoke Test

1. Use aerosol simulated smoke, such as ESL Smoke! In a Can® (ESL

Part No. SM-200) to perform the smoke test.

The LED will remain on while the built-in transmitter sends an alarm signal,
and the sensor will produce a three-beep pattern.
2. Press the test/silence button to end the test.
The sensor automatically resets when smoke is no longer present. A
sensor that fails to activate may require cleaning. If a sensor still fails to
activate after cleaning, return the unit for service.

3.2 Sensitivity Test

1. Press and hold the test button for four seconds, then release it. The

LED will flash corresponding to the sensor’s sensitivity.

During this test, the control panel, serial receiver or network coordinator
should receive an alarm and a low battery signal, if low battery is selected,
followed a few seconds later by a restoral.
If the control device fails to respond, it is possible the EN1242 failed to
reset properly when the batteries were installed. To force a reset, remove
the batteries from the EN1242 for a least 30 seconds, reinstall them, press
the reset button, then retest as described above.

4 Clean the EN1242

Clean the sensor cover with a dry or damp cloth as needed to keep it free
from dust and dirt. Clean the sensor interior and replace the optical
chamber at least once each year. Use only ESL model 211 optical
chambers for replacement. To clean the sensor chamber:
1. Remove the sensor body from the mounting base.
2. Remove the batteries.
3. Slide a flat-blade screwdriver in the slot on the sensor cap and gently

push the handle down to pry the cap off.

4. Squeeze the optical chamber where indicated and pull it up and away

from the sensor. Discard.

Flashes

Sensor Condition/Action

1

Self-diagnostics failure. Return sensor for service/
replacement.

2-3

Sensor is becoming insensitive. Clean the sensor (see
“Clean the EN1242”) and retest. If error persists, replace
sensor.

4-7

Sensor is within normal sensitivity range.

8-9

Sensor is becoming too sensitive. Verify that the smoke
chamber is snapped down securely. Clean the sensor and
retest.

Advertising