Inovonics EE4204 User Manual

Ee4204 echostream, Receiver, 2 installation and startup

Advertising
background image

© Inovonics, 2011 - www.inovonics.com

EE4204 EchoStream

®

Receiver

Installation Instructions - 05426F

1 Overview

The EE4204 receiver allows you to add up to four transmitters to any
application. With diversity reception and advanced signal processing,
Inovonics Wireless EchoStream technology is designed to minimize dead
spots in transmission areas.

1.1 Inovonics Wireless Contact Information

If you have any problems with this procedure, contact Inovonics Wireless
technical services:

• E-mail: [email protected]
• Phone: (800) 782-2709; (303) 939-9336

1.2 EE4204 LEDs and Buttons

Figure 1 Receiver LEDs and Buttons

Most of the LEDs and buttons perform different function depending on
which mode the EE4204 is in.

Normal Operation Mode

Alarm LED: Lights when any transmitter is sending an alarm transmission.
Tamper Fault LED: Lights when any transmitter is sending a tamper
transmission.
Low Battery Fault LED: Lit when any transmitter has a low battery.
Inactive Fault LED: Lit when any transmitter is inactive.
Power LED: Lit when receiving power.
Transmitter Number LEDs: Lit when the transmitter is in alarm.
Advance Button: Press the Advance button to enter status review mode.
Decode LED: Flashes when any recognizable transmission is received.
This LED is only visible when the pry-out door or cover is removed.
Reset Button: Clears the current status for all points and resets all outputs
and LEDs. Resets the supervision window timers. This button is only
accessible when the pry-out door or cover is removed.

Status Review Mode

Alarm LED: Lights when the selected transmitter is sending an alarm
transmission.
Tamper Fault LED: Lights when the selected transmitter is sending a
tamper transmission.
Low Battery Fault LED: Lit when the selected transmitter has a low
battery.
Inactive Fault LED: Lit when the selected transmitter is inactive.
Power LED: Lit when receiving power.
Transmitter Number LEDs: Shows status of the transmitter assigned to
that number when lit. Use the advance button to scroll through transmitters.
Advance Button: Scrolls through transmitters to display status.
Decode LED: Flashes when any recognizable transmission is received.
This LED is only visible when the pry-out door or cover is removed.
Reset Button: Clears the current status for all points and resets all outputs
and LEDs. Resets the supervision window timers. This button is only
accessible when the pry-out door or cover is removed.

1.3 EE4204 Internal Components

Figure 2 EE4204 Components

2 Installation and Startup

2.1 Connect Power Cabling

Before beginning startup, you will have to connect power to the receiver. To
connect power to the receiver:
1. Connect power cabling to the Power and GND connections.

• Power source should be 11-14 VDC. Power supply must be

unswitched, uninterrupted, and regulated.

2.2 Enable EchoStream Select

To meet ETSI requirements, Inovonics has developed a new line of EE
868MHz-only products. These new 868MHz-only products are compatible
with older systems that include EchoStream Select (ES) products. If you
are using any ES products in your current system, you will need to enable
EchoStream Select compatibility on this new 868MHz-only product.
To enable/disable EchoStream Select compatibility:
1. To enable compatibility with ES products, place a selection jumper on

the ES selection pins.

Note: Selection jumpers are included in the EE4204 hardware packet.

2. If no ES products are used in your system, remove the selection jumper

from the ES selection pins.

3. Cycle power.

2.3 Program the Receiver

Note: If changing programming for a point that already has a transmitter
registered to it, there is no need to re-register the transmitter. Changes to
point programming are automatically assigned to the transmitter registered
to that point.

The default settings are:

A Alarm LED

B Tamper Fault LED

C Low Battery Fault LED

D Inactive Fault LED E Power LED

F Transmitter Number LEDs

G Advance Button

H Decode LED

I Reset Button

A

B

D

E

F

G

C

H

I

A Housing release

tabs

B Power (11-14

VDC)

C Ground connection

D Output terminals

E Fault output

F Advance button

G Reset button

H Reset input

I Jam output

J Tamper output

K Program button

L EchoStream Select

compatibility selection pins

M Decode LED

Point Supervision

Window

Output Type

Switch
(EE4204
Only)

1

4 hours

1

Follow

N/O

2

4 hours

2

Follow

N/O

3

4 hours

3

Follow

N/O

4

4 hours

4

Follow

N/O

F

N/A

Fault

Inactive is set to follow; low
battery and tamper are set
to latching.

N/O

A

B

C

D

I

J

H

L

E

A

A

G

F

K

M