Receiver operation, Warning: to clear a latched fault or alarm, press, Activated led – Inovonics FA404 User Manual

Page 5: Reset, Fa404r, 3-way configuration panel, Resistor provided with hardwire panel

Advertising
background image

© 1998 Inovonics Wireless Corporation LIT-FA404-INSTALL

5

02327C.DOC 8-Oct-01

Receiver Operation:

Output activation: The FA404 has N/O open collector Alarm and Fault outputs. Output is open relative to ground.

On activation, output pulls to common ground. The FA404R has Form C Alarm and Fault relay outputs. Output

activation is indicated by illumination of the

ACTIVATED LED

. Note: if a receiver is being connected to a normally

closed zone, the FA404R must be used.

Connection to hardwire panels: When an FA404 or FA404R receiver is used with a hardwire security panel, the

panel will typically supply power and ground to the receiver. When the ground supplied to the receiver is common

to the return loops of the hardwire panel, use one wire to connect each of the FA404 receiver outputs to the zone

input of the panel. Supervision resistors in N/O loops must be placed in parallel. Supervision resistance in N/C

loops must be in series. The examples below show typical connections of both the FA404 and the FA404R.

13.6V

GND

N/C

N/O

COM

13.6V

GND

N/C

COM

N/O

N/C

N/O

F

A

UL
T

A

L

A

RM

13.6VDC

GROUND

FAULT SUPERVISION ZONE

NOTE: GROUND AND
RETURNS ARE COMMON.

FA404

PANEL

RETURN

ALARM ZONE

EOL resistors, if required

13.6V

GND

N/C

N/O

COM

13.6V

GND

N/C

COM

N/O

N/C

N/O

FA
U

L

T

AL
A

R

M

13.6VDC

GROUND

ALARM ZONE

FAULT ZONE RETURN

ALARM ZONE RETURN

FAULT SUPERVISION ZONE

FA404R, N/O configuration

PANEL

NOTE: GROUND AND
RETURNS ARE NOT
COMMON.

EOL resistors, if required
for N/O configuration

13.6V

GND

N/C

N/O

COM

13.6V

GND

N/C

COM

N/O

N/C

N/O

F

A

UL
T

A

L

A

RM

13.6VDC

GROUND

ALARM ZONE RETURN

FA404R, N/C configuration

PANEL

NOTE: GROUND AND
RETURNS ARE NOT
COMMON.

FAULT ZONE RETURN

FAULT ZONE

ALARM ZONE

EOL resistors, if required
for N/C configuration

WARNING: To clear a latched fault or alarm, press

RESET

. Make sure that the receiver is not in program mode

or the transmitter will be deleted. Test all transmitters prior to leaving the site.


If the panel has N/O zones and can recognize 3 zone conditions (open=fault, short=alarm and EOL
resistance=normal), both the alarm and the fault outputs can be attached to the same zone as shown below.

13.6V

GND

N/C

N/O

COM

13.6V

GND

N/C

COM

N/O

N/C

N/O

FA
U

L

T

AL
A

R

M

13.6VDC

GROUND

ZONE INPUT

FA404R, 3-WAY CONFIGURATION

PANEL

NOTE: GROUND AND
RETURNS ARE NOT
COMMON.

COMMON

Resistor provided with
hardwire panel