Data processing time – KEYENCE DL-PN1 User Manual

Page 23

Advertising
background image

21

- PROFINET Communication Unit DL-PN1 User's Manual (GT) -

Data Processing Time

The data update time for data I/O communication is shown below.

Maximum data processing time = (1) + (2) + (3) + (4)

(1) I/O controller data update time
(2) Network data update time
(3) Data update time between the DL-PN1 and sensor amplifiers

(4) Sensor amplifier response time

For (1) and (2), see manuals for each model.
For (4), refer to the User's Manual of each sensor amplifier connected to the DL-PN1.

(4)

(3)

(2)

(1)

DL-PN1

LINK

/ACT

RST

SF

BF

DL

Sensor amplifier

master

Sensor amplifier with calculation function OFF,
or sensor amplifier with no calculation function

Sensor amplifier with calculation function ON

Number of

connected sensor

amplifiers

Output, judgment value, or

current value

Number of

connected sensor

amplifiers

Output, judgment value, or

current value

GT-70A series*

GT-70A series*

1

7.8 ms

1

11.3 ms

2

9.8 ms

2

14.3 ms

3

13.8 ms

3

20.3 ms

4

15.8 ms

4

23.3 ms

5

19.8 ms

5

29.3 ms

6

21.8 ms

6

32.3 ms

7

25.8 ms

7

38.3 ms

8

27.8 ms

8

41.3 ms

9

31.8 ms

9

47.3 ms

10

33.8 ms

10

50.3 ms

* Cannot be connected to GT-70 series.

* Cannot be connected to GT-70 series.

Advertising