3 communication methods, Co mm u ni c a ting w ith t he fd -s s er ie s – KEYENCE DL-CL1 User Manual

Page 46

Advertising
background image

3-3 Communication Methods

3-18

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-S

s

er

ie

s

3

Current values can be read in the monitor modes and full modes. They cannot be
read in small-memory modes. Instantaneous flow rate is read as the current value
regardless of the detection mode setting.

Monitor mode 1

When reading current values in monitor mode 1, specify the ID numbers (in terms of
current value page numbers) of the sensor amplifiers to be read to current value
boxes 1 to 3. For details of the current value box numbers and current value page

numbers used for specifying ID numbers, see

"Device Maps" (page 3-4).

When reading current values in monitor mode 2 or full mode, see

"Monitor mode

2/full mode" (page 3-19).

This example illustrates how to read the current values from the sensor amplifiers of ID 01/02/03 and ID
07/08/09.
(1) Specify the page numbers in "select current value box page number" and execute "request to change

current value page".

(2) After the current values of the specified current value pages are read, the "current value page

change complete" signal flips from 0 to 1.

(3) The "current value page change error" signal flips from 0 to 1 if an error occurs during the current

value change process. Check the values specified in the "select current value box page number"
parameter.

(4) The property of each current value is entered. Check that each current value is normal value, "over"

(FFFF), or "invalid" (----).

Reading Current Values (Instantaneous Flow Rate) from Sensor Amplifiers

PLC

Sensor amplifier

Select current value box page number 0(Current value page 0)

2 (Current value page 2)

RWw08

Request to change current value page

RY5E

Current value page change complete

RX5E

Current value page change error

RX5F

Current value property

Each bit of RWr07

Current value: box 1

1234

8901

5678

RWr08

Current value: box 2

2345

9012

6789

RWr0A

Current value: box 3

3456

7890

RWr0C

Current value of ID 01 1234 8901

Current value of ID 02

2345

9012

Current value of ID 03

3456

Current value of ID 07

5678

Current value of ID 08

6789

Current value of ID 09

7890

1

1

1

1

0

0

0

0

(1)

(6)

(2)

(3)

(4)

(5)

(7)

(7)

Advertising