If *;5 is fixed at 0.5% of F.S., the presence or absence of hysterisis

can be selected by the extended function (page 16).

„

Free range analog output

Set the pressure value for the respective free range analog start

point and end point. The function of the output 2 can be selected at

the time of #P.) (analogue output). #52 and #'2 can be set freely

within the measured range. Operation is as follows.

1. When #52 < #'2

• When #52 becomes #'2: 4 mA

becomes 20 mA

• If the measurement value falls below

#52

, output will be up to 3.8 mA

• If the measurement value rises above

#'2

, output will be up to 20.5 mA

2. When #52 > #'2

• When #52 becomes #'2: 4 mA

becomes 20 mA

• If the measurement value falls below

#'2

, output will be up to 20.5 mA

• If the measurement value rises above

#52

, output will be up to 3.8 mA

The name of the setting values depending on the mode

and output are as follows.

When system error ('T5) occurs, 2 mA will be output.