2.4 Instruction Details

1

2

3-121

Chapter 2 Instructions

ITVL

A/D data measurement
Turns ON output relay 0500 when the analog input from the KL-4AD to DM1600
(range: 1 to 5 V) exceeds +3 V. Turns ON output relay 0501 when the input is below
+2 V. Writes the average into DM0100.
Refer to the "KL-4AD/KL-2AD User’s Manual" for data memory settings for the KL-
4AD.

Coding

2008

2008

2008

2008

2003

0001

0002

1000

#01600

LDA

DM0000

STA

#02000

LDA

DM0001

STA

#01000

LDA

DM0002

STA

#00100

LDA

DM0003

STA

PLS

DM0000

PAUSE

1000

RES

ITVL

1001

1003

DM0100

STA

DM0007

LDA

0500

0501

Writes average into DM0100 every 100 measurement.

Measures contents of DM1600.

Sets max. setting value to +3 V (2000).

Sets min. setting value to +2 V (1000).

Sets number of averaging measurements to 100.

Pauses measurement when input relay 0001 turns ON.
Resets measurement when input relay 0002 turns ON.

0500 turns ON when measured value exceeds max. setting value.

0501 turns ON when measured value is below min. value.

Line No.

Instruction

Operand

Line No.

Instruction

Operand

0000

LD

2008

0014

CON

0001

LDA

#01600

0015

STA

DM0003

0002

CON

0016

LD

2003

0003

STA

DM0000

0017

LD

0001

0004

LD

2008

0018

LD

0002

0005

LDA

#02000

0019

ITVL

DM0000 1000

0006

CON

0020

LD

1000

0007

STA

DM0001

0021

OUT

0500

0008

LD

2008

0022

LD

1001

0009

LDA

#01000

0023

OUT

0501

0010

CON

0024

LD

1003

0011

STA

DM0002

0025

LDA

DM0007

0012

LD

2008

0026

STA

DM0100

0013

LDA

#00100