AERCO Belimo AF120-S US Actuator User Manual

Installation instructions

Advertising
background image

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA

55

Dimensions (Inches [mm])

min. 3 1/2"

[90]

min. 3/4"

[20]

IND-AF2 Position Indicator

(optional)

Remove
for 3/4”
to 1.05”
shafts

IND-AF2 Position Indicator

(optional)

Installation Instructions

Quick-Mount Visual Instructions for Mechanical Installation

Quick-Mount Visual Instructions

1. Rotate the damper to its fail-safe position.

If the shaft rotates counterclockwise, mount the “CCW” side of the actuator out.
If it rotates clockwise, mount the actuator with the “CW” side out.

2. If the universal clamp is not on the correct side of the actuator, move it to the correct side.

3. Slide the actuator onto the shaft and tighten the nuts on the V-bolt with a 10mm wrench to 6-8 ft-lb of torque.

4. Slide the anti-rotation strap under the actuator so that it engages the slot at the base of the actuator. Secure the strap to the duct work with #8 self-tapping screws.

NOTE: Read the “Standard Mounting” instructions, on the next page, for more detailed information.

M40024 - 05/10 - Subject to change.