AERCO Belimo AMX24-MFT Actuator User Manual

AERCO Equipment

Advertising
background image

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA

362

Installation and Operation

Non-Spring Return

General Information

Preliminary Steps

1. Belimo actuators with NEMA 1 or NEMA 2 ratings should be mounted indoors in

a dry, relatively clean environment free from corrosive fumes. If the actuator is
mounted outdoors, a protective enclosure must be used to shield the actuator.

2. For new construction work, order dampers with extended shafts. Instruct the

installing contractor to allow space for mounting the Belimo actuator on the shaft.

For replacement of existing gear train actuators, there are two options:
A. From a performance standpoint, it is best to mount the actuator directly onto the

damper shaft.

B. If the damper shaft is not accessible, mount the non-spring return actuator with

a ZG-NMA or ZG-GMA crank arm kit, and a mounting bracket (ZG-100, ZG-101,
ZG-103, ZG-104)

Determining Torque Loading and Actuator Sizing

Damper torque loadings, used in selecting the correct size actuator, should be pro-
vided by the damper manufacturer. If this information is not available, the following
general selection guidelines can be used.

Damper Type

Torque Loading

Opposed blade, without edge seals, for
non-tight close-off applications

3 in-lb/sq. ft.

Parallel blade, without edge seals, for
non-tight close-off applications

4 in-lb/sq. ft.

Opposed blade, with edge seals, for tight
close-off applications

5 in-lb/sq. ft.

Parallel blade, with edge seals, for tight
close-off applications

7 in-lb/sq. ft.

The above torque loadings will work for most applications under 2 in. w.g. static
pressure or 1000 FPM face velocity. For applications between this criteria and 3 in.
w.g. or 2500 FPM, the torque loading should be increased by a multiplier of 1.5. If
the application calls for higher criteria up to 4 in. w.g. or 3000 FPM, use a multiplier
of 2.0.

Torque Loading Chart

140

120

100

80

60

40

20

0

2

3

4

6

8

10

5

7

9

Damper

Area (sq. ft.)

Torque Loading (in-lb/ sq. ft.)

Multiple Actuator Mounting

If more torque is required than one GM can provide, GM24B, GMB24-SR or GMX24-
MFT may be installed on the same shaft.

Table of Contents

PAGE

General Mounting
Standard .............................................................270
Reversible

Clamp ................................................271

Linear .................................................................272

Rotary .................................................................273

Retrofit Brackets .................................................275

Operation

Electrical .............................................................276

Mechanical .........................................................277

Wiring
General ...............................................................278
Accessories ........................................................279

Startup and Checkout ..............................................282

M40024 - 05/10 - Sub

ject to chan

g

e.

© Belimo

Aircontrols

(USA

), Inc.

Advertising