Installation – AERCO BMK 1.5 LN Dual Fuel Jan 2009 User Manual

Page 18

Advertising
background image

INSTALLATION

2-8

• Network (RS485 Modbus. See para. 2.10.7)

While it is possible to control a boiler or boilers
using one of the previously described modes of
operation, it may not be the method best suited
for the application. Prior to selecting one of
these modes of operation, it is recommended
that you consult with your local AERCO
representative or the factory for the mode of
operation that will work best with your
application. For more information on wiring the
4 to 20 mA / 1 to 5VDC or the 0 to 20 mA / 0 to 5
VDC, see paragraph 2.9.3.

2.9.5 Combination Mode

NOTE

Only BMS Model 168 can be utilized for
the Combination Mode, not the BMS II
(Model 5R5-384).

With a Combination Mode unit, field wiring is
between the unit’s I/O Box wiring terminals, the
CCP (Combination Control Panel), and the BMS
Model 168 (Boiler Management System). The
wiring must be accomplished using twisted-
shielded pair wire from 18 to 22 AWG. Polarity
must be maintained. For further instructions and
wiring diagrams, refer to the GF-108 Boiler
Management System Operations Guide and the
CCP-1 data sheet.

2.10 I/O BOX CONNECTIONS

The types of input and output signals and
devices to be connected to the I/O Box terminals
shown in Figure 2-10 are described in the
following paragraphs.

CAUTION

DO NOT make any connections to the
I/O Box terminals labeled “NOT
USED”. Attempting to do so may
cause equipment damage.

2.10.1 OUTDOOR SENSOR IN

An outdoor air temperature sensor (AERCO Part
No. 122790) will be required primarily for the
Indoor/Outdoor reset mode of operation. It can
also be used with another mode if it is desired to
use the outdoor sensor enable/disable feature.
This feature allows the boiler to be enabled or
disabled based on the outdoor air temperature.

The factory default for the outdoor sensor is
DISABLED. To enable the sensor and/or select
an enable/disable outdoor temperature, see the
Configuration menu in Chapter 3.

The outdoor sensor may be wired up to 200 feet
from the boiler. It is connected to the
OUTDOOR SENSOR IN and SENSOR
COMMON terminals in the I/O Box (see Figures
2-9 and 2-10). Wire the sensor using a twisted
shielded pair wire from 18 to 22 AWG. There is
no polarity to observe when terminating these
wires. The shield is to be connected only to the
terminals labeled SHIELD in the I/O Box. The
sensor end of the shield must be left free and
ungrounded.

When mounting the sensor, it must be located
on the North side of the building where an
average outside air temperature is expected.
The sensor must be shielded from direct sunlight
as well as impingement by the elements. If a
shield is used, it must allow for free air
circulation.

2.10.2 AUX SENSOR IN

The AUX SENSOR IN terminals can be used to
add an additional temperature sensor for
monitoring purposes. This input is always
enabled and is a view-only input that can be
seen in the Operating Menu. The sensor must
be wired to the AUX SENSOR IN and SENSOR
COMMON terminals and must be similar to
AERCO BALCO wire sensor Part No. 12449. A
resistance chart for this sensor is provided in
Appendix C.

2.10.3 ANALOG IN

The ANALOG IN + and – terminals are used
when an external signal is used to drive the
firing rate (Direct Drive Mode) or change the
setpoint (Remote Setpoint Mode) of the Boiler.

Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA
/ 0 to 5 VDC signal may be used to vary the
setpoint or firing rate. The factory default setting
is for 4 to 20 mA / 1 to 5 VDC, however this may
be changed to 0 to 20 mA / 0 to 5 VDC using the
Configuration Menu described in Chapter 3. If
voltage rather than current is selected as the
drive signal, a DIP switch must be set on the
PMC Board located inside the Control Box.
Contact the AERCO factory for information on
setting DIP switches.

All of the supplied signals must be floating
(ungrounded) signals. Connections between the
signal source and the Boiler’s I/O Box must be
made using twisted shielded pair wire from 18 to
22 AWG, such as Belden 9841 (see Figure
2-10). Polarity must be maintained. The shield
must be connected only at the source end and
must be left floating (not connected) at the
Boiler’s I/O Box.

Advertising