4.2.1 Required Tools & Instrumentation

The following tools and instrumentation are necessary to perform combustion calibration of the
unit:

• Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and

Nitrogen Oxide (NOx) resolution to 1PPM.

• 16 inch W.C. manometer or equivalent gauge and plastic tubing.
• 1/4 inch NPT-to-barbed fittings for use with gas supply manometer or gauge.
• Small and large flat blade screwdrivers.
• Tube of silicone adhesive

4.2.2 Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to monitor the gas pressure on the downstream
side of the SSOV during the Combustion Calibration procedures described in section 4.3.

The gas supply manometer is installed at the upstream and/or downstream location shown in
Figure 4-1.



Figure 4-1:

BMK 1500/2000: 1/4 Inch Gas Plug Location for Combustion

Calibration

NATURAL
GAS INLET

SSOV

TO

AIR/FUEL

VALVE

LEAK DETECTION

BALL VALVE

1/4” NPT PLUG

(Install manometer here for
Combustion Calibration)

HIGH GAS
PRESSURE
SWITCH

LOW GAS
PRESSURE
SWITCH

MANUAL

SHUT-OFF

VALVE

Advertising