Appendix A

Benchmark 2.0LN Low NOx Boiler

GF-123

Menu Items Installation, Operation and Maintenance Manual

OMM-

0046_0F

Page 124 of 172

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12

Table A-1: Boiler Menu Item Descriptions-Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists
between the setpoint temperature and the actual outlet
temperature. If the actual error is less than the
proportional band setting (1 to 120°F), the fire rate will
be less than 100%. If the error is equal to or greater
than the proportional band setting, the fire rate will be
100%.

Integral Gain

This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each minute to
move towards the setpoint. Gain is adjustable from
0.00 to 2.00. Default is 1.00 for boilers.

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of
change of the setpoint error. This is the time that this
action advances the output.

WARMUP: The feature embodied in the following three menu items eliminates
Temperature Overshoots during the “Warmup” period of a cold ignition cycle on all
boilers by temporarily modifying the PID Gain parameter during warmup and for a period
defined in the Tuning Menu

Warmup Prop Band

Range = 1-120

Default = 95

Warmup Int Gain

Range = 1-200

Default = 50

Warmup PID Timer

Range = 1-240

Default = 20

Reset Defaults?

Allows Tuning Menu options to be reset to their Factory
Default values.