CONTROL PANEL OPERATING PROCEDURES
Table 3-6.
Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas
Fire Rate,
Air/Fuel Valve
Position
(% Open)
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
0 0 0
10% 0
0
18%
(Stop Level)
100,000
5.0%
20%
134,000 7%
30%
349,000 17%
40%
631,000 32%
50%
893,000 45%
60%
1,150,000 58%
70%
1,410,000 71%
80%
1,610,000 81%
90%
1,830,000 92%
100%
2,000,000 100%