APPENDIX K

K-2

K-1. NATURAL GAS COMBUSTION
CALIBRATION

The combustion calibration procedures provided
in this Appendix apply only to Benchmark 3.0LN
units with serial numbers below G-07-1901.

All Benchmark 3.0LN Boilers are combustion
calibrated at the factory prior to shipping.
However, recalibration as part of initial start-up
is necessary due to changes in the local altitude,
gas BTU content, gas supply piping and supply
regulators. Factory Test Data sheets are
shipped with each unit. These sheets must be
filled out and returned to AERCO for proper
Warranty Validation.

It is important to perform the following procedure
as outlined. This will keep readjustments to a
minimum and provide optimum performance.

1. Open the water supply and return valves to

the unit and ensure that the system pumps
are running.

2. Open the natural gas supply valve(s) to the

unit.

Figure K-1

Regulator Adjustment Screw Location

3. Set the control panel ON/OFF switch to the

OFF position.

4. Turn on external AC power to the unit. The

display will show LOSS OF POWER and the
time and date.

11. Raise the firing rate to 100% and verify that

the gas pressure downstream of SSOV No.
1 remains at 1.5” W.C. Readjust pressure if
necessary.

5. Set the unit to the Manual Mode by pressing

the AUTO/MAN key. A flashing Manual Fire
Rate

message will be displayed with the

present rate in %. Also, the MANUAL LED
will light.

12. With the firing rate at 100%, insert the

combustion analyzer probe into the flue
probe opening and allow enough time for the
combustion analyzer to settle.

6. Adjust the fire rate to 0% by pressing the ▼

arrow key.

13. Compare the measured oxygen level to the

oxygen range for the inlet air temperature
shown in Table K-1. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.

7. Ensure that the leak detection ball valve

down-stream of SSOV No. 2 is open.

8. Set

the

ON/OFF switch to the ON position.

9. Change the fire rate to 29% using the ▲

arrow key. The unit should begin its start
sequence and fire.

Table K-1

Combustion Oxygen Levels for a 100%

Firing Rate

10.

Next, verify that the gas pressure
downstream of SSOV No. 1 is 1.5” W.C. for
both FM and IRI gas trains. If gas pressure
adjustment is required, remove the brass
hex nut on downstream SSOV No. 1
containing the gas pressure regulator
(Figure K-1). Make gas regulator adjust-
ments using a flat-tip screwdriver to obtain
1.5” W.C.

Inlet Air

Temp

Oxygen %

± 0.2

Carbon

Monoxide

NOx

>100°F

4.8 %

<100 ppm

<30 ppm

90°F

5.0 %

<100 ppm

<30 ppm

80°F

5.2 %

<100 ppm

<30 ppm

<70°F

5.3 %

<100 ppm

<30 ppm