Vermont castings dvr28 direct vent gas fireplace, Below grade installations – Vermont Casting DVR28IN User Manual

Page 15

Advertising
background image

20012301

15

Vermont Castings DVR28 Direct Vent Gas Fireplace

The Vent Graph shows the relationship between vertical
and horizontal side wall venting and will help to deter-
mine the various dimensions allowable.
Minimum clearance between vent pipes and com-
bustible materials is 2”(51 mm) on top and 1” (25
mm) on the bottom and sides unless otherwise
noted.
When vent termination exits through foundations less
than 20” below siding outcrop, the vent pipe must
flush up with the siding. It is always best to locate the
fireplace in such a way that minimizes the number of
offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace to the face of
the outer wall.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.

When installing the appliance as a rear
vent unit, the 90° or 45° transition elbow
is NOT INCLUDED in the following criteria
and calculations, and unless specifically
mentioned should be ignored when calcu-
lating venting layouts.

The maximum number of 90° elbows per side wall
installation is three (3). (Fig. 20)

FP1755
Horizontal Run
2/07

A 10’

(254 cm)

B 7’

(178 cm)

8’

(244 cm)

A + B = 17’

(518 cm) Max.

FP1755

Fig. 21 Maximum vent run with elbows.

If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914 mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise. (Fig. 21)

Example: According to the vent graph (Page 11) the
maximum horizontal vent length in a system with a 7.5’
(2.3 m) vertical rise is 20’ (6 m) and if a 90° elbow is
required in the horizontal vent it must be reduced to 17’
(5.2 m). In Figure 21 Dimension A plus B must not be
greater than 17’ (5.2 m).
In Figure 21, dimension A plus B must not be greater
than 17’ (5.2 m).

The maximum number of 45° elbows permitted per
installation is six (6). These elbows can be installed
in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (45 cm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system
is 270°. (Fig. 22)

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total angular variation = 270°

Below Grade Installations

When it is not possible to meet the required vent ter-
minal clearances of 12” (305 mm) above grade level
a snorkel kit is recommended. This allows installation
depth of down to 7” (178 mm) below grade level. The
7” is measured from the center of the horizontal vent
pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed.
If venting system is installed below ground, we recom-
mend a window well with adequate and proper drainage
to be installed around the termination.

Fig. 20 Maximum three (3) 90° elbows per installation.

������
������������
����

3 x 90°

Elbows

FP1754

Transition
Elbow

1
2
3
4

������
�������������
����

1 + 2 + 3 + 4 = 270°

FP1756

Fig. 22 Maximum elbow usage.

Transition Elbow

Advertising