INITIAL START-UP

4-8

6. Install the correct VFD Logic Stick for the

fuel being used.

7. Remove the manometer and barbed fittings

and reinstall the NPT plug using a suitable
pipe thread compound.

8. Remove the combustion analyzer probe

from the vent hole. Replace the NPT plug in
the vent hole using a suitable pipe joint
compound.

9. Replace the unit’s side panels and front

door.

4.6 OVER-TEMPERATURE LIMIT
SWITCHES

The unit contains both automatic and manual
reset over-temperature limit switches. These
switches are mounted on a plate attached to the
boiler shell as shown in Figure 4-6. The switches
can be accessed by removing the left side
panels of the unit. The manual reset switch is
not adjustable and is permanently fixed at
210°F. This switch will shut down and lock out
the boiler if the water temperature exceeds
210°F. Following an over-temperature condition,
it must be manually reset by pressing the
RESET button before the boiler can be
restarted. The automatic reset over-temperature
switch is adjustable and allows the boiler to
restart, once the temperature drops below its
temperature setting. Set the automatic over-
temperature switch to the desired setting.

Figure 4-6

Over Temperature Limit Switch

Locations