MAINTENANCE

7-5

RELIEF VALVE

DRAIN VALVE

REDUCING

1/4" PLUG

HOT WATER

HOT WATER

SUPPLY (OUTLET)

RETURN (INLET)

BUSHING

REDUCING

BUSHING

Figure 7.9

Heat Exchanger Supply and Return

Locations

4. Remove the 2 ½ inch plug located in the

shell at the rear of the unit (Figure 7.10).

5. Remove the relief valve, drain valve (Figure

7.9) and any reducing bushings.

6. Perform the inspection. Reassemble the unit

once the inspection is completed.

7. Open the supply and return valves and

reconnect AC power to the unit.

2-1 /2 INCH

PLUG

Figure 7.10

Heat Exchanger 2 ½ Inch Inspection Plug

Location

7.8 Condensate Drain Assembly

KC Boilers contain a condensate drain cup

(Figure 2.6) which should be inspected and

cleaned annually to ensure proper operation.

To inspect and clean the assembly, proceed as

follows:

1. Remove the left side panel and left rear

cover to provide access to the condensate

drain components (see Figure 2.6).

2. Disconnect the plastic tubing from the

condensate cup drain tube to the drain.

3. Remove the condensate cup from the unit.

Thoroughly clean the cup and inspect the

cup drain tube for blockage.

4. After the above items have been cleaned

and inspected, reassemble the drain

components by reversing the previous

steps.