Electronic Control System (ECS) and Type CXT-E Valve

3. ADJUSTMENT

VD2: 02/28/14 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Page 27 of 82

AC-105

OMM-0003_0D

3.3 ELECTRONIC CONTROL SYSTEM (ECS) ADJUSTMENT

The Electronic Control System (ECS) is preset at the setpoint temperature specified on the
Sales Order. The over-temperature alarm limit is normally set 20°F above the specified setpoint.
If no setpoint or over-temperature alarm limit is specified, the ECS will be set to the Factory
Default values of 140°F (setpoint) and 160°F (over-temperature alarm limit). If changes are
required, the setpoint and over-temperature alarm limits can be easily changed. This is
accomplished using the controls provided on the Temperature Controller and the Over-
Temperature Switch contained in the Control Box shown in Figure 3-2. These items can be
viewed through the window on the front door of the Control Box. To access these controls and
adjust the setpoint or over-temperature alarm limit, open the hinged Control Box door. Proceed
as follows to adjust the required parameters:

NOTE:

For “Water-to-Water” Heater applications, two additional
Temperature Display Indicators are mounted below the Over Temp
Switch. Although these Indicators are identical to the Over Temp
Switch, they are “Indicator-Only” devices which cannot be adjusted.

WATER HEATER

TEMP CONTROLLER

B-PLUS

TM

HOLD

RUN

AUTO

MAN

2408

PT.NO.

PT.NO.

OVER TEMP SWITCH

PANEL
DOOR

OVER-TEMP
SWITCH

TEMPERATURE

CONTROLLER

Figure 3-2. Control Box – Front View

NOTE:

When the Power Switch on the Control Box is set to the ON position,
it also energizes the internal DC Power Supply in the Control Box.
This in turn provides 24 VDC power to the Control Valve Actuator,
provided that the water temperature at the heater outlet is below the
high temperature limit setting.