AERCO ECS Retrofit User Manual

Page 44

Advertising
background image

44

BOILER WATER

OUTLET

BOILER WATER

INLET

CXT-E

CONTROL

VALVE

BOILER WATER

INLET SENSOR

LOCATION

BOILER WATER

OUTLET SENSOR

LOCATION

VALVE SPOOL

PIECE ASSEMBLY

VALVE SPOOL

PIECE ASSEMBLY

Figure 4-9. E-Plus Boiler Water Inlet and Outlet Temperature Sensor Locations

4.4.2 Double-Wall Water Heaters
The sensor installation locations for a Water-to-Water Model DW-24 differ slightly from the locations
used for DW-45 and DW-68 Models as shown in Figure 4-10. DW-45 and DW-68 Sensors are
mounted on the Boiler Water Inlet and Outlet Flanges. However, since these flanges do not exist for
the DW-24, the Sensors are mounted on the bottom of the Boiler Water Inlet and Outlet as shown in
Figure 4-10. Install the Boiler Water Inlet and Outlet Sensors as follows for the Model being retrofitted:

1. Check to ensure that the capillary tubes and compression fittings have been removed from the

Boiler Inlet and Outlet Flanges shown in Figure 4-10. If they have not been previously remove,
disconnect and remove these items at this time.

2. For DW-45 and DW-68 Models, install the Boiler Water Inlet Temperature Sensor in the

tapped opening in the Boiler Water Inlet Flange shown in Figure 4-10. For a DW-24 Model,
install the Sensor in the tapped hole at the bottom of the Boiler Water Inlet as shown.

3. For DW-45 and DW-68 Models, install the Boiler Water Outlet Temperature Sensor in the

tapped opening in the Boiler Water Outlet Flange shown in Figure 4-10. . For a DW-24 Model,
install the Sensor in the tapped hole at the bottom of the Boiler Water Inlet as shown.

4. The electrical connector plugs on the Inlet and Outlet Boiler Water Temperature Sensors will

be connected after the ECS Control Box is installed (paragraph 4.5).