Troubleshooting – AERCO KC1000 Heater Mar 2011 User Manual

Page 68

Advertising
background image

TROUBLESHOOTING

7-4

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

FFWD TEMP

SENSOR FAULT

1. Loose or broken wiring.

2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect feed forward (BTU transmitter)

sensor for loose or broken wiring.

2. Check resistance of sensor to determine if it

is within specification.

3. Ensure that the correct sensor is installed.

FLAME LOSS

DURING RUN

1. Worn Flame Detector or

cracked ceramic.

2. Defective Differential

Regulator.

3. Poor combustion calibration.
4. Debris on burner.

5. Blocked condensate drain.

1. Remove and inspect the Flame Detector for

signs of wear or cracked ceramic. Replace if

necessary.

2. Check gas pressure readings using a gauge

or manometer into and out of the Air/Fuel

Valve to ensure that the gas pressure into

and out of the valve is correct.

3. Check combustion calibration. Adjust as

necessary.

4. Remove the burner and inspect for any

carbon or debris. Clean and reinstall.

5. Remove blockage from condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand Relays on

the Ignition/Stepper (IGST)

board failed to activate when

commanded

2. Relay is activated when not in

Demand

1. Press CLEAR button and restart the unit. If

the fault persists, replace IGST Board.

2. Defective relay. Replace IGST Board.

HIGH EXHAUST

TEMPERATURE

1. Defective exhaust sensor.

2. Carboned heat exchanger due

to incorrect combustion

calibration

1. Measure the actual exhaust temperature and

continuity of the exhaust sensor. If the

exhaust temperature is less than 500

o

F and

the exhaust sensor shows continuity replace

the sensor.

2. If exhaust temperature is greater than 500

o

F, check combustion calibration. Calibrate or

repair as necessary.

HIGH GAS

PRESSURE

1. Incorrect supply gas pressure.

2. Defective Supply Regulator or

Wrong Style Regulator

1. If using a non-lock up style regulator for the

gas supply, measure static gas pressure

downstream, it should be 14”WC or less.

Adjust as necessary.

2. If gas supply pressure cannot be lowered, a

lock-up style regulator may be required or the

supply regulator may be defective.

Advertising