APPENDIX A

FAULT MESSAGES

FAULT MESSAGE

FAULT DESCRIPTION

HIGH WATER TEMP

SWITCH OPEN

The High Water Temperature Limit Switch is open.

LOW WATER

LEVEL

The Water Level Control board is indicating low water level.

LOW GAS

PRESSURE

The Low Gas Pressure Limit Switch is open.

HIGH GAS

PRESSURE

The High Gas Pressure Limit Switch is open.

INTERLOCK

OPEN

The Remote Interlock is open.

DELAYED

INTERLOCK OPEN

The Delayed Interlock is open.

AIRFLOW FAULT

DURING PURGE

The Blower Proof Switch opened during purge.

PRG SWTCH OPEN

DURING PURGE

The Purge Position Limit switch on the air/fuel valve opened

during purge.

IGN SWTCH OPEN

DURING IGNITION

The Ignition Position Limit switch on the air/fuel valve opened

during ignition.

IGN SWTCH CLOSED

DURING PURGE

The Ignition Position Limit switch on the air/fuel valve closed

during purge.

PRG SWTCH CLOSED

DURING IGNITION

The Purge Position Limit switch on the air/fuel valve closed

during ignition.

AIRFLOW FAULT

DURING IGN

The Blower Proof Switch opened during ignition.

AIRFLOW FAULT

DURING RUN

The Blower Proof Switch opened during run.

SSOV

SWITCH OPEN

The SSOV switch opened during standby.

SSOV FAULT

DURING PURGE

The SSOV switch opened during purge.

SSOV FAULT

DURING IGN

The SSOV switch closed or failed to open during ignition.

SSOV FAULT

DURING RUN

The SSOV switch closed for more than 15 seconds during

run.

SSOV RELAY

FAILURE

A failure has been detected in one of the relays that control

the SSOV.

FLAME LOSS

DURING IGN

The Flame signal was not seen during ignition or lost within 5

seconds after ignition.

FLAME LOSS

DURING RUN

The Flame signal was lost during run.

HIGH EXHAUST

TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

LOSS OF POWER

A power loss had occurred. The time and date when power

was restored is displayed.