Installation Instructions

Issue Date March 12, 2010

©

2010 BASO Gas Products.

1

Part No. BASO-INS-BG1600M51EF-1AA, Rev. D

www.baso.com

BG1600M51EF-1AA Universal

Intermittent Pilot Ignition Control

Application

The BG1600M51EF-1AA Universal Intermittent Pilot
Ignition Control replaces many existing intermittent
pilot ignition controls made by various
manufacturers. It is a safety control designed for
indirect burner ignition and supervision, for use with
all gases and applicable to gas-fired appliances.

The BG1600M51EF-1AA is a microprocessor based
ignition control. The microprocessor provides reliable
software control of all timings and operates a
diagnostic Light-Emitting Diode (LED). It provides
ignition sequence, flame monitoring, and safety
shutoff for intermittent pilot boilers, furnaces and
other heating appliances. For a complete listing of
specifications, refer to the Technical Specifications
section.

Installation

Parts Included

The BG1600M51EF-1AA is supplied with a parts kit
containing:
• 6 labels for marking wires

• 1/4” terminal for sense wire

• 3 wire nuts

• Rajah adapter described below
This control uses 1/4” quick connect terminals for
spark connection. If existing cable uses Rajah or
1/4” female spark plug connector, use the adapter
shown in Figure 1.

Figure 1: Rajah Adapter

IMPORTANT:

Only qualified personnel

should install or service BASO Gas Products®.
These instructions are a guide for such personnel.
Carefully follow all instructions for the appliance.

IMPORTANT:

Make all gas installations in

accordance with applicable local, national, and
regional regulations.

!

WARNING: Risk of Explosion or Fire.

Do not install the control in an area that is exposed
to water (for example, dripping, spraying, rain). Do
not use the control if it has been exposed to water.
Exposure to water may cause malfunction and can
lead to an explosion or fire and may result in
severe personal injury or death.

IMPORTANT:

Verify that the control being

replaced is in Table 1 or confirm it is a suitable
replacement using the specifications of the
BG1600M51EF-1AA.

IMPORTANT:

This control is approved for

use with noise suppression (resistive) spark wires.
If the application has copper wire, it must be
replaced.

The BG1600M51EF-1AA replaces existing
intermittent pilot ignition controls listed in Table 1 or
controls with the following specifications:

• flame detection using flame rectification

technology (ability of a flame to conduct and
rectify current)

• Single rod (local sense) or dual rod (remote

sense) flame sensing

• 100% shutoff/lockout with 5 minute continuous

retry

• trial times of 25 seconds or longer
• prepurge period 1 second or less
• main burner 400,000 BTU/hr maximum
• pilot burners with flow rates of 1,500 Btu/hr or

less

• with or without automatic vent damper
• must be used with redundant gas valves and not

subjected to temperatures below -40˚F (-40˚C)
or above 170˚F (77˚C)