Provide power, 2connect your wires 3 – Braeburn 7320 Installer Guide User Manual

Page 3

Advertising
background image

3 Installer Guide

Provide Power

C

24VAC Power Terminal (C)

2

Connect Your Wires

3

+

+

For 24 Volt AC power, you must connect the common side of the transformer to the C terminal on the thermostat
sub-base. In dual transformer installations, the transformer common must come from the cooling transformer.
• For battery power, insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear
housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with
the +/- symbols in the battery compartment.
• If connecting this thermostat to a Wi-Fi network, a 24 VAC common (C wire) is required.

Batteries Installed as Shown

Terminal

Function

Description

Rc

Input

24 Volt AC Cooling Transformer

(Dual Transformer Systems Only)

Rh

Input

Power Connection (24 Volt AC

Heating Transformer)

C

Input

24 Volt AC Transformer Common

W2 / AUX

Output

(W2) 2nd Stage Conventional Heat

(AUX) Auxiliary Heat (Heat Pump)

W1 / E

Output

(W1) 1st Stage Conventional Heat

(E) Emergency Heat

L

Input

System Malfunction Indicator

A

Output

Economizer, Fresh Air or Output Control

O / B

Output

(O) Cool Active Reversing Valve

(B) Heat Active Reversing Valve

G

Output

Fan Control

Y2

Output

2nd Stage Compressor

Y1

Output

1st Stage Compressor

K

-

Optional Share-a-Wire

TM

module connection

S2
S1

Input

Optional Wired Remote Sensor

(indoor or outdoor)