INSTALLATION INSTRUCTIONS

MODEL 169000

AIR FILTER GAUGE

APPLICATION

PRECAUTIONS

INSTALLATION

(Figure 1)

AIR
FILTER

BLOWER

RETURN
AIR

GAUGE

INSTALL CLEAN

FILTER, RUN

BLOWER AND

ADJUST GAUGE

POINTER TO

CLEAR AREA

IN CENTER

OF GREEN

UP

DOWN

FILT

ER

IS

CL

EA

N

C

H

A

N

G

E

F

IL

T

E

R

AIR FILTER GAUGE

Indoor Air Quality Products

AIR FILTER GAGE

INSTALL CLEAN

FILTER, RUN

BLOWER AND

ADJUST GAGE

POINTER TO

CLEAR AREA

IN CENTER

OF GREEN

UP

DOWN

FILT

ER

IS

CL

EA

N

C

H

A

N

G

E

F

IL

T

E

R

The 169000 Air Filter Gauge provides a visual indication of the need to replace the air filters in forced air heating and cooling

systems. The gauge is installed between the blower and the filter where a slight vacuum exists due to the air flow resistance

of the air filter. Air flowing into the gauge, around the calibration screw, lifts a vane in proportion to the negative pressure in

the blower compartment. As the air filter loads, the vacuum increases, raising the vane to indicate a filter change

is necessary.
The gauge may be calibrated in a negative pressure range from 0.1 to 0.4 inch w.c. When properly calibrated in this range a

vacuum increase of 0.10 to 0.15 inch w.c. will indicate a filter change is necessary.

The installer should be an experienced service technician. When drilling the hole

in the blower compartment extreme care should be taken not to damage

components within the heating or cooling system.

OPTIONAL REMOTE INSTALLATION

(Figure 2)

FIELD SUPPLIED:

One (1) piece of 5/16” (inside diameter) vinyl tubing up to 10

feet in length, and three (3) #4-24 x 1” screws.

1. Select a location on the blower compartment between the air filter and the

blower and drill a 7/16" diameter hole. Insert one end of the vinyl tubing

about 2" into the hole.
2. On a wall, enclosing the furnace room for example, mark a position where

the filter gauge can be easily seen and is within reach of the vinyl tube.
3. Drill a 1/2" diameter hole through the wall and feed the vinyl tube through

the hole. Keep overall length of tubing used as short as possible.
4. Push the three plastic retainer clips out from the back of the gauge with a

blunt tool. They will be replaced with the three #4-24 x 1" screws included.
5. Push the vinyl tubing over the pressure sensing tube of the gauge and

move the gauge back against the wall in a level position. Drill three 3/32"

diameter holes through the gauge holes. Drive the three screws to hold the

gauge in place. Do not overtighten.
6. See “CALIBRATION”.

Figure 1

Figure 2

1. The gauge must be located where it can sense pressure conditions in the

blower compartment between the filter and the blower. Select a location on

a vertical surface enclosing the blower compartment and drill a 3/8" hole.
2. Remove the protective paper from the foam adhesive strip on the back

of the gauge.
3. Mount the gauge in a level position with the pressure sensing tube

projecting into the blower compartment.
4. See “CALIBRATION”.