C&D Technologies 41-7525 VRLA Batteries (rack mounted systems) User Manual

Page 6

Advertising
background image

Storage Instructions

Store batteries in a clean, dry cool area away from radiant heat sources. Elevated storage temperatures
increase the self-discharge rate of the batteries and reduces the storage time between required
freshening charges. Fully charged batteries with an electrolyte specific gravity of 1.280 or higher can
be safely stored at temperatures as low as -20 degrees F.

Batteries in storage should be given a freshening charge at 2.4 volts per cell for 24 hours every 6
months or when the open circuit voltage declines to 2.07 volts per cell (6.2 and 12.4 volts for 6 and 12
volt batteries respectively).

Additional details concerning storage and inventory control are contained in the document "Self
Discharge and Inventory Control", technical bulletin #41-7272.

Preparation of

Battery System

Installation

Drawings

(User

Prepared)

Rack

Assembly

and

Installation

Receipt and

Inspection of

Battery

System

Components

Unpacking and

Transporting

Battery

System

Cells

Storage of

Battery

System

Components

Required

Detailed Intercell

Connection and

Cable Termination

Drawings

Placement of

Cells on

Rack and

Installing

Intercell

Connections

Installing

Intertier,

Interrow and

Intrarack

Cable

Connections

Installing

Battery System

to Charger/

Rectifier/Load

Cable

Connections

Pre-Operational

Checkout and

Initial

Freshening

Charge

Complete

Cell/Unit

Retaining

Rail

Installation

Operational

Qualification

Checkout

and

Warranty

Registration

Seismic

Rack

To

Storage

Standard

Rack

Figure 3 - 12V VRLA Battery System Installation Task Flow Chart

41-7525/0514/CD 6 www.cdtechno.com

Advertising