VIII. Initial Installation Data

The following initial installation data should be maintained on site:

• Date and Initial open circuit voltage of unit(s) at time of delivery to the site.

• Freshening charge records, if performed.

• Initial torque value used for connections.

• Overall system float voltage across battery terminals.

• Individual unit float voltage.

• Internal Ohmic value of each unit.

• Connection resistances.

• Float current.

IX. Periodic Maintenance

These VRLA batteries are maintenance free with respect to the electrolyte. However, the charging voltage,
temperature, performance and connection resistances must be periodically monitored and any necessary
corrective actions taken if irregular values are observed to assure reliable standby power when required.

Quarterly Inspection

• Measure and record the system total float charging voltage at the battery terminals

• Record the charger on charge output current and voltage

• Record the ambient temperature and condition of ventilation equipment

• Visually inspect the batteries and rack for general appearance, cleanliness or any irregularity.

• If gas tubing provisions are utilized, check for any obstructions in the tubing which would prevent

the free flow of gases thru the exit point.

Semiannual Inspection

• Repeat the quarterly checks

• Record the on charge voltage of each unit

• Optionally perform and record Ohmic checks for trending purposes

Yearly and Initial Inspection

• Repeat the semiannual checks

• Inspect all connections to ensure integrity.









Any data, descriptions or specifications presented herein are subject to revision by
C&D Technologies, Inc. without notice. While such information is believed to be accurate
as indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all
warranties, express or implied, with regard to the accuracy or completeness of such
information. Further, because the product(s) featured herein may be used under
conditions beyond its control, C&D Technologies, Inc. hereby disclaims all warranties,
either express or implied, concerning the fitness or suitability of such product(s) for any
particular use or in any specific application or arising from any course of dealing or usage
of trade. The user is solely responsible for determining the suitability of the product(s)
featured herein for user’s intended purpose and in user’s specific application.
Copyright 2014 C&D TECHNOLOGIES, INC. Printed in U.S.A. RS-2046 0514/CD