Check operation, Sta№up and check-off, How it works – Whirlpool CHCH8WS User Manual

Page 6: With service switch in “on” position, How it works-malfunction light

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

CHECK OPERATION

STA№UP AND CHECK-OFF

1.

Start the unit by opening water valve and turning the

service switch to "ON ”

2.

NOTE: In "CLEAN" position, only the water pump

operates.

3.

Check water level in pump pan. When not running,

water level should be VA" deep.

4.

Check for even water flow over freezing plate. Unit

must be level for proper operation.

5. Check freezing plate to make sure it is getting cold.

6.

Check cutter grids. Interior temperature limiter above

top grid turns grids "OFF" above 130° F.

7.

Check for desired cube thickness and adjust if neces­

sary. Maximum capacity will be obtained with ice thick­
ness at 1/2" to 5/8". Do not adjust less than 3/8" thick as
machine may malfunction.

8. Replace all panels.

9. Store ice scoop m a clean place.

PUMP
MOTOR

HOW IT WORKS

WITH SERVICE SWITCH IN “ON” POSITION

1. Contactor is energized

2. Compressor runs

3. Condenser fans run

4. Water pump runs

5. Thickness control motor runs

6. Cutter grid warm to touch

NOTE: Grids

will be

'OFF ' until temperature limiter

inside cabinet cools to 130° F.

WHEN DESIRED ICE SLAB THICKNESS IS

REACHED, HARVEST CYCLE BEGINS WITH THE
FOLLOWING RESULTS:

1.

Thickness control arm raises, actuating switch and

holding relay coil

2. Compressor keeps running

3. Hot gas solenoid valve is energized and opens

4. Condenser fans stop
Condenser water valve closes tightly (Water cooled)

5. Thickness control motor keeps running

6. Water pump stops

7. Water siphons from pump pan and refills

8.

Cutter grid warm to touch

MACHINE THEN GOES BACK INTO FREEZE
CYCLE WHILE SLAB IS BEING CUT INTO CUBES

ON CUTTER GRID

WHEN STORAGE BIN GETS FULL, BIN BAFFLE
OPENS SWITCH.

1. Slab completion relay keeps machine in freeze cycle until
full ice thickness is reached.

2.

Machine then shuts completely off leaving slabs to

defrost by ambient temperature.

3. Cutter grids are "OFF."

HOW IT WORKS-MALFUNCTION LIGHT

1. When the high side pressure raises above the safe

operating limits the machine will shut down because the
blocked

condenser

thermostat

or

pressure

control

opened and the light will come on.

On air cooled models — this indicates that the condenser
is blocked with dirt and must be cleaned or the con­
denser fan motor is not moving air through the finned
condenser.

On water cooled models — this indicates the condenser
has excessive scale inside, water pressure is low, or
water has been shut off.

NOTE:

After

correcting

the

malfunction,

manually

reset

the control.

Advertising
This manual is related to the following products: