Gas supply requirements – Kenmore 64182 User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ià WARN ING

I

Exceeding the length of duct pipe or number

of elbows allowed in the “MAXIMUM LENGTH" charts

can

cause an accunnulation of lint in the exhaust systenn. Plugging
the systenn could create a fire hazard, as well as increase drying
tinnes.

ià WARNING

Do not screen the exhaust ends of the vent

system, nor use any screws, rivets or other fastening means

that extend into the duct and catch lint to assemble the
exhaust system.

Lint can beconne caught in the screen, on the

screws or rivets, clogging the duct work and creating a fire hazard
as well as increasing drying tinnes. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct tape.
All male duct pipe fittings MUST

be installed downstream with

the flow of air.

ik WARNING

Explosion hazard. Do not install the dryer

where gasoline or other flammables are kept or stored.

If

the dryer is installed in a garage, it must be a minimum of 18

inches (45.7 cm) above the floor. Failure to do so can result in
death, explosion, fire or burns.

Number

of

90°

Turns

MAXIMUM LENGTH

of 4" (10.2 cm) Dia. Rigid Metai Duct

VENT HOOD TYPE

(Preferred)

(10.2 cm)

Louv ired

i

5

^k-

(6.35 cm)

0

60 ft.(18.28 m)

48 ft. (14.63 m)

1

52 ft.(15.84 mi

40 ft. (12.19 mi

2

44 ft.(13.41 m)

32 ft. (9.75 m)

3

32 ft.(9.75 m)

24 ft. (7.31 mi

4

28 ft. (8. S3 m)

16 ft. (4.87 mi

Number

of

90°

Turns

MAXIMUM LENGTH

of 4" (10.2 cm) Dia. Fiexibie Metai Duct

VENT HOOD TYPE

(Preferred)

(10.2 cm)

Louvt^red

i

5

^k-

(6.35 cm)

0

30 ft. (9.14 m)

18 ft. (5.49 m)

1

22 ft. (6.71 mi

14 ft. (4.27 mi

2

14 ft. (4.27 mi

10 ft. (3.05 mi

3

NOT RECOMMENDED

than 0.75 inches of water column, the system is acceptable.

If the manometer reading is higher than 0.75 inches of water
column, the system is too restrictive and the installation is
unacceptable.

Although vertical orientation of the exhaust system is acceptable,
certain extenuating circumstances could affect the performance
of the dryer:

Only the rigid metal duct work should be used.

Venting vertical through a roof may expose the exhaust system
to down drafts causing an increase in vent restriction.

Running the exhaust system through an uninsulated area may

cause condensation and faster accumulation of lint.

Compression or crimping of the exhaust system will cause an
increase in vent restriction.

The exhaust system should be inspected and cleaned a minimum
of every 18 months

with normal usage. The more the dryer is

used, the more often you should check the exhaust system and

vent hood for proper operation.

EXHAUST DIRECTION
All dryers shipped from the factory are set up for rear exhausting.

However, on electric dryers, exhausting can be to the right or left

side of the cabinet or the bottom of the dryer. On gas dryers,
exhausting can be to the right side of the cabinet or the bottom of
the dryer. Directional exhausting can be accomplished by installing

Exhaust Kit, P/N 131456800, available through your parts

distributor. Follow the instructions supplied with the kit.

EXHAUST DUCT LOCATING DIMENSIONS

GAS SUPPLY REQUIREMENTS

A WARNING

Replace copper connecting pipe that is not

plastic-coated. Stainless steel or plastic-coated brass MUST

be used.

INSTALL MALE FITTINGS IN CORRECT DIRECTION

In installations where the exhaust system is not described in the
charts, the following method must be used to determine if the
exhaust system is acceptable:

1. Connect an inclined or digital manometer between the

dryer and the point the exhaust connects to the dryer.
Set the dryer timer and temperature to air fluff (cool down)
and start the dryer.

Read the measurement on the manometer.

The system back pressure MUST NOT be higher than 0.75

inches of water column. If the system back pressure is less

1

Installation MUST

conform with local codes, or in the absence

of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition).
The gas supply line should be of 1/2 inch (1.27 cm) pipe.
If codes allow, flexible metal tubing may be used to connect
your dryer to the gas supply line. The tubing MUST

be

constructed of stainless steel or plastic-coated brass.
The gas supply line MUST

have an individual shutoff valve.

A 1/8 inch (0.32 cm) N.RT plugged tapping, accessible for
test gauge connection, MUST

be installed immediately

upstream of the gas supply connection to the dryer.

The dryer MUST be disconnected from the gas supply piping
system during any pressure testing of the gas supply piping
system at test pressures in excess of 1/2 psig (3.45 kPa).
The dryer MUST be isolated from the gas supply piping system
during any pressure testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig (3.45 kPa).

Advertising
This manual is related to the following products: