TESTING AND OPERATION

After installation and wiring, to check the operation of heating
systems:
1.
Disconnect power.
2. Place the heat/cool selector switch, if applicable, in the heat

position.

3. Adjust the setpoint ten or more degrees below the temperature

of the controlled space.

4. Restore power.
5. Slowly adjust the setpoint upward. When the setpoint reaches

the approximate temperature of the controlled space, the heat-
ing equipment should start.

To check the operation of the cooling systems:
1.
Disconnect power.
2. Place the heat/cool selector switch, if applicable, in the cool

position.

3. Adjust the setpoint ten or more degrees above the temperature

of the controlled space.

4. Restore power.
5. Slowly adjust the setpoint downward. When the setpoint

approximates the temperature of the controlled space, the cool-
ing equipment should start.