Troubleshooting, Recalibrate thermometer – Honeywell CT5OC User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TROUBLESHOOTiNG

Your Honeywelf thermostat requires little or no attention. Most problems car generally be traced to the following:

NOTE: If your system is heating-only or air conditioning-only, disregard sections not applicable to your system.

SYMPTOM

No heat

Furnace turns on

and off.

Major swings in
t e m p e r a t u r e
(greater than 2° F
[1'" C| when out­
side temperature

is stable).

PROBLEM

System switch at OFF or
COOL Position.

Blown fuse or tripped
circuit breaker.

Furnace power switch is

on OFF.

No pilot name.

Improper connections to

thermostat.

Defective

thermostat.

(Here’s how you teil:

Remove the thermostat
trom the wall. Discon­
nect wire from W ter­
minal, Touch W wire to

R terminal. The thermo­

stat is detective if the
burner comes on.)

Other,

Burner ON period is too
short.

B u r n e r O N
is too long

p e r i o d

CORRECTIVE ACTION

Move switch to HEAT

position.

Replace fuse or reset

circuit breaker.

Switch to ON.

Relight pilot flame per
furnace

manufacturer’s

instructions,

With power to furnace
OFF, tighten at I mounting
and terminal screws. Re­
pair frayed or broken
wires.

Exchange the thermostat

(see Warranty).

Contact a qualified service

technician for assistance.

Remove the thermostat
cover and move the heat

anticipator lever COUNTER­

CLOCKWISE

one

scale mark. Replace the
cover and ivait several

hours for the system to

stabilize.

Remove the thermostat
cover and move the heat

anticipator lever CLOCK­
WISE

one scale

mark. Replace the cover

and wait several hours for
the system to stabilize.

SYMPTOM

PROBLEM

CORRECTIVE ACTION

Thermostat setting
and thermometer
reading disagree.

Thermostat is not level.

Recheck the ihermostat
position on wall. Use a
bubble level to make sure
it's level. See step 4,

Thermostat affected by
drafts or radiant heal.

Contact a qualified service
technician to change the
location. The thermostat
should be about 5 ft [1.5
m] above the floor and on

an inside wall.

Thermostat is out of cali­
bration.

Contact a qualified service
technician to recalibrate
the thermostat-

Thermometer is out of

calibration.

Recalibrate See step 8.

No air condition­
ing.

System switch in in OFF

or HEAT position.

Move switch to COOL
position.

Blown fuse or tripped

circuit breaker.

Replace fuse or reset
circuit breaker.

Compressor switch (lo­
cated outdoors} is turned

OFF

Move switch to ON posi­

tion.

Improper connections to
thermostat

With power to furnace
OFF, tighten all mounting
and terminal screws, Re­
pair broken wires.

Defective thermostat.

(Here’s how you tell:

Remove the thermostat

from wall Disconneci
wire from V terminal
Touch Y wire to terminal
R. The thermostat is de-
feclive if the compressor
starts. Some systems
have a time delay, so
allow at least 5 minutes,)

See caution in section 6.

Exchange the thermostat.

See Warranty.

Other

Contact service techni-

cian for assistance.

RECALIBRATE THERMOMETER

If the ihermostat set point and the

thermometer reading do not agree, the
thermometer may need recalibration.

Follow the procedure below.

Remove thermostat cover.

Set the cover on a table rear an
accurate thermometer.

After allowing 5 or 10 minutes for

stabilization, compare the read-

ings.

It the readings are the same,

replace cover and put the system

into operation.

If the readings are different, insert

a hex-head wrench in the ther­

mometer shaft and turn it until the
thermometers have the same reading.

Replace cover and put the system
into operation.

Advertising
This manual is related to the following products: