WARNING: Hazard of Electric Shock. Disconnect all
power before installing heater.

Note: These heaters are designed for wall or ceiling mounting
only. Other modes of mounting voids factory warranty.
1. Height above floor

A. In areas where ceiling height is more than 12 feet, recom-

mended mounting height is approximately 10 feet to under-
side of heater.

B. For ceiling heights of 12 feet or less, maximum mounting

height is determined by use of ceiling mounting brackets
offered for these heaters. Minimum spacing to ceiling is 3”
(see Figure 2).

C. In either case, minimum mounting height is 7 feet from

floor to bottom of heater (see Figures 1 and 2).

2. Spacing to adjacent walls

A. Rear of case to back wall 4-7/8” minimum (see Figure 2).
B. Side of case to side wall 6” minimum (see Figure 2).

3. If two or more units are operated in the same enclosed space,

their discharges should be directed to aid in development of
mass air movement for uniform heat dispersal.

4. Controlling thermostats to individual heaters should be

mounted at shoulder height on inside walls or columns.

‡ Models with suffix “T” added (480 volts only) are equipped with a transformer, 480 volt primary — 120/240 volt secondary.
‡ Models with suffix “R” added are equipped with a relay (Example: UB-1002E-R 240 volt or 480 volt — 3 phase only).

Horizontal

Model

Volts and Phase

kW

Air

Discharge

UB-1002E

208 - 240 - 480 (1 or 3)

10

40’

UB-1252E

208 (3) - 240 (3) - 480 (1 or 3)

12.5

40’

UB-1502E

208 (3) - 240 (1 or 3) - 480 (1 or 3)

15

45’

UB-2002E

240 (1 or 3)

19.9

45’

UB-2002E

208 (3) - 480 (1 or 3)

20

45’

Specifications —

Dimensions —

Rubber Feet Provided for

Wall Mount Model Only.

7/8” and 1-23/32”
Dia. Holes in Rear

13-3/4”

17-1/8”

20-3/4”

11-3/4”

9-5/16”

For Lower Height
from Ceiling:
Customer to Add
Extention Strap

12-1/4”

8”

6”

7’-0” Min.

Height Above

Floor

Figure 1

Mounting UB using

Ceiling Mounting

Brackets*

Ceiling Line

Wall

Back

Wall

6” Min. Spacing to

Adjacent Wall

3”

4-7/8”

Min.

11-3/4”

17-11/16”

7’-0” Min. Height

Above Floor

Mounting

Holes Center

10”

8”

Figure 2

Mounting UB using Wall

Mounting Brackets*

*Wall and/or Ceiling Mounting Brackets are
available as an accessory option — Contact
your local sales representative.

Type UB-1002E, UB-1252E, UB-1502E, UB-2002E

Forced-Air Heaters