Table 5 — Piping Components (cont)

LEGEND

*Check all system component pressure ratings (coils, values,

pumps, etc.) with manufacturer and any applicable local or national
piping codes prior to specifying system pressure rating.

NOTES:

1. Motorized 2-way valves have a maximum close-off differential

of 25 psi.

2. Motorized 3-way valves have a maximum close-off differential

of 10 psi.

SYMBOL/SKETCH

DESCRIPTION

C

V

FACTOR

RATING*

STEAM

USE

1

/

2

in.

3

/

4

in.

PSI

F

STRAINER: Y-type body with 50 mesh stain-
less steel screen.
Application — Used for removal of small parti-
cles from system water during normal system
operation. Should not be used in lieu of main
system strainers. Strainer screen may have to
be removed during initial high pressure sys-
tem flushing during start-up. Screen should be
removed and cleaned per normal mainte-
nance schedule (provisions for strainer blow-
down not provided).

9.0

Clean

19.0

Clean

400

250

N/A

GATE VALVE: Manual shut-off valve.
Application — Used for unit isolation during
system flushing, servicing, etc. Do not use for
water balancing.

19.8

36.0

200

200

NO

GLOBE VALVE: Standard pattern, manual
shut-off and throttling valve.
Application — Used for unit isolation. Not rec-
ommended for high flow rates due to relatively
high pressure drop.

1.8

3.9

200

200

NO

COMPRESSION STOP VALVE:
Manual shut-off valve.
Application — Used for unit isolation during
system flushing, servicing, etc. Not recom-
mended for high flow rates due to relatively
high pressure drop.

2.3

5.4

150

200

NO

BALL VALVE: Manual balance and shut-off
valve.
Application — Used for unit isolation and
water flow balancing. Without memory stop
feature water balance point must be marked
by installer (if necessary). Check specifica-
tions for service fittings required when used
for water balancing.

4.0

7.5

400

200

YES

BALL VALVE WITH MEMORY STOP:
Manual balance and shut-off valve.
Application — Used for unit isolation and
water flow balancing. The adjustable memory
stop feature allows return to the balance point
after shut-off. Check specifications for
service fittings required when used for water
balancing.

4.0

7.5

400

200

N/A

Cv — Coefficient of Velocity
DX — Direct Expansion

Advertising
This manual is related to the following products:

42D, 42S