I/o

EXPANSION CAPABILITY

EX250

One (1) expansion unit can be connected to each EX250 controller. A total of 16 I/O slots are available. If

32 point I/O modules are used, all the discrete I/O can be located on the controller leaving the expansion
unit available for register type I/O (Analog, PID, BCD, etc.)

Local I/O

• 2S6 points or
• 32 registers

EX500

Three (3) expansion units can be connected to each EX500 controller. A total of 32 I/O slots are available.

If 32 point I/O modules are used, all the discrete I/O can be located on the controller and the first

expansion unit leaving the last two expansion units available for register type I/O (Analog, PID, BCD,
etc.).

Local I/O

• 512 points or
• 64 registers

Notes: 1) A 0.5 m expansion cable is shipped with each expansion unit. Optional I m expansion cables are

also available. Total cable length should be less than 2 m.

2) Four types of expansion units are available

EU-6237

480 mm width, 8 ilou, with AC power »upply

EU*6257D

480 mm width, 8 slots, with DC power supply

EU-6279

390 mm width, 8 slots, no power supply

EU-6278

240 mm width, 4 slots, no power supply, tentiiiution only

If total 5 Vdc current consumption will exceed 4.5 A, the expansion unit with power supply

must be used.