Chapter 2. IO-Link Port Configuration

IO-Link Master Modbus/TCP Reference Manual: 2000590 Rev. A

Editing IO-Link Settings

2.1.1. Editing IO-Link Settings

You can use this procedure to configure IO-Link characteristics for each port. The following table or help
system provides information about each option.

1.

If necessary, open the IO-Link Master web interface with your web browser using the IP address or
through PortVision DX.

2.

Click Configuration in the menu bar, which by default loads the IO-Link Settings page.

3.

Click the EDIT button for the port that you want to configure.

4.

Make appropriate selections for the IO-Link device that you will connect to that port. You can use the help
system if you require definitions or values for the options or

2.1.2. IO-Link Settings Parameters

on Page

14.

5.

Click the SAVE button.

6.

Repeat for each port that requires configuration changes.

2.1.2. IO-Link Settings Parameters

The IO-Link Settings configuration page supports the following options.

IO-LINK SETTINGS Page

Port Name

User defined port or device description.

Standard ASCII characters

Max length = 80 characters

Port Mode

Default: IO-Link

Selected IO-Link Port Mode. Valid settings are:

Reset

IO-Link

Digital In

Digital Out

Invert IO

Default: False

If enabled and the Port Mode is Digital In or Digital
Out, inverts the I/O value.

0= False (Disabled - Do not invert IO)

1= True (Enabled - Invert IO)

Note: Does not affect the Auxiliary Input.

Minimum Cycle Time

Default: 4

The minimum, or fastest, cycle time that the IO-Link
device may operate at. The valid range is 4-65535 ms.