Comtrol Modbus Server User Manual

Page 29

Advertising
background image

DeviceMaster Modbus Server User Guide: 2000535 Rev. C

Embedded Web Pages - 29

Edit Port Configuration Page

Name

Value(s)

Description

Serial Configuration

Mode

All models, except 2-port
models:

RS-232 (default)

RS-422

RS-485

2-port models:

RS-232 (default)

RS-422

RS-485_2-wire

RS-485 4-wire Master

RS-485 4-wire Slave

Selectable serial mode of communications.

Baud Rate

300, 600, 1200, 2400,
4800, 9600, 19200, 38400
(default), 57600, 115200,
230400

Selectable serial port baud rates.

Parity

None (default)

Even

Odd

Selectable parity values.

Data Bits

5, 6, 7, 8 (default)

Selectable data bit values.

Stop Bits

1(default) or 2

Selectable stop bit values.

Flow

None (default)

RTS/CTS

XON/XOFF

Half-Duplex

Selectable flow control values.

Rx Timeout Between
Packets

0-65535

(default = 50)

Receive time-outs between packets in
milliseconds. This is the maximum spacing
between received bytes allowed before
Modbus/RTU messages/responses received
over both the serial and Ethernet TCP/IP
interface are expected to be complete.

Note: If this value is set too low, incomplete

and/or invalid Modbus/RTU
messages may be incorrectly detected.

Duplicate Serial
Configuration For All
Ports

N/A

If selected, will apply the serial port
configuration to all serial ports.

Modbus/RTU Protocol Settings

Device Response
Timeout

0 to 65535 ms.

(Default=1000 ms)

The maximum allowable time for a slave
Modbus/RTU to respond to a message before
the message is considered timed out.