Operating instructions

R4E250-BA09-03

Translation of the original operating instructions

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

If you have any other problems, contact ebm-papst.

5.1 Cleaning

NOTE
Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

5.2 Safety test

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean or
replace impeller

Item no. 10714-5-9970 · Revision 82623 · Release 2014-05-08 · Page 10 / 10