Operating instructions

K3G250-AY11-C4

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

PE

PE

Protective earth connection

KL1

1, 2, 3

L1, L2, L3

Supply voltage, voltage range (see type plate), 50/60 Hz

KL2

1

NC

Floating status contact, break with error

KL2

2

COM

Floating status contact, changeover contact, common connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

KL2

3

NO

Floating status contact, close with error

KL3

1

OUT

Analogue output, 0-10 VDC, max. 3 mA, SELV,
Output of the actual motor duty cycle (PWM):
1 V corresponds to 10% PWM,
10 V correspond to 100% PWM.

KL3

2, 8

GND

Signal ground for control interface, SELV

KL3

3, 7

0-10 V

Set value / actual sensor value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV

KL3

4

+10 V

Voltage output 10 VDC (+/-3%), max. 10 mA,
power supply for external devices (e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA, supply voltage for external devices
(e.g. sensors), SELV

KL3

6

4-20 mA

Set value / actual sensor value input 4-20 mA, impedance 100 Ω, only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for MODBUS, RSB

KL3

10, 12

RSA

RS485 interface for MODBUS, RSA

Item no. 52836-5-9970 · ENG · Revision 82624 · Release 2014-11-17 · Page 9 / 12