Operating instructions – ebm-papst A3G630-AD03-A8 User Manual

Page 9

Advertising
background image

Operating instructions

A3G630-AD03-A8

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1,2

PE

green/
yellow

Protective earth

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, normally closed connection (2 A, max. 250 VAC, min. 10 mA)

1

6

NC

white 2

Floating status message contact, normally closed connection

2

8

0 - 10 V

yellow

Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV

2

11

10 VDC

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50611-5-9970 · Revision 82624 · Release 2014-05-08 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Advertising