Operating instructions – ebm-papst W4E450-CU03-01 User Manual

Page 5

Advertising
background image

Operating instructions

W4E450-CU03-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M4E094-EA

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed / min

-1

1300

1490

Power input / W

350

425

Current draw / A

1.55

1.87

Motor capacitor / µF

8

8

Capacitor voltage / VDB

450

450

Max. back pressure / Pa

120

50

Min. ambient temperature
/ °C

-40

-40

Max. ambient
temperature
/ °C

55

45

Starting current / A

6.0

5.5

Maximum safe operating
speed / min

-1

1950
@ 55 °C

1950
@ 55 °C

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

32.9

26.6

30.6

Efficiency grade N

42.3

36

40

Power input P

e

/ kW

0.33

Air flow q

v

/ m³/h

3920

Pressure increase total p

sf

/ Pa

100

Speed n / min

-1

1325

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

9.6 kg

Size

450 mm

Surface of rotor

Coated in black

Material of terminal box

ABS plastic, black

Material of blades

Press-fitted sheet steel blank, sprayed
with PP plastic

Material of wall ring

Sheet steel, pre-galvanised and coated in
black plastic

Material of guard grille

Steel, phosphated and coated in black
plastic

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box, integrated capacitor
connected via terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

CE

Approval

CCC; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 11739-5-9970 · Revision 82623 · Release 2014-05-08 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Advertising