MECHANICAL COOLING LOCKOUT — Determine the
outdoor-air temperature at which you want the mechanical
cooling (compressors) to be disabled. Locate the mechanical
cooling lockout (MECH CLG LOCKOUT) potentiometer. To
disable this feature, turn the potentiometer counterclockwise
(CCW) to the OFF position. Otherwise, set the value between
10 and 60 F. Mechanical cooling will not operate when the out-
door air temperature is below this value. See Fig. 16.

DRY BULB CHANGEOVER SET UP — Determine the dry
bulb changeover set point from Table 5. The settings are A, B,
C and D. Locate the ECON SP potentiometer and set the dry
bulb changeover set point. See Fig. 16. When the OAT is above
this set point, the damper is limited to minimum position
setting.

If a potentiometer fails, its setting will default to the values

in Table 6.

Table 4 — EconoMi$er Switchover Control Strategy

*Must be selected manually.

Table 5 — Changeover Set Points

*Field-installed accessory.

Table 6 — Default Potentiometer Settings

ECONOMI$ER SWITCHOVER

STRATEGY

SENSORS REQUIRED

Outdoor Air Temperature

Outdoor Air Enthalpy

Return Air Temperature

Return Air Enthalpy

Dry Bulb

X

Single Enthalpy

X

Differential Temperature

X

X

Differential Enthalpy*

X

X

SETTINGS

A

B

C

D

Dry Bulb (°F)

73

69

66

63

Single Enthalpy* (Btu/lb)

27

25

24

22

Differential Temperature*
(°F, Not Adjustable)

2

2

2

2

Differential Enthalpy*
(Btu/lb, Not Adjustable)

1

1

1

1

POTENTIOMETER

DEFAULT SETTING

CO

2

SP (PPM)

1,000

MECH CLG LOCKOUT

50 F

ECON SP

D

MIN POS (%)

20

LEGEND

*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO

2

are field-installed accessories.

Fig. 23 — Typical EconoMi$er Sensor Wiring

COM

Common

DAT

Discharge Air Thermistor

DM

Damper Motor

GND

Ground

OAH

Outdoor-Air Enthalpy Sensor

OAT

Outdoor-Air Temperature Sensor

POT

Potentiometer

RAH

Return-Air Enthalpy Sensor

RAT

Return-Air Temperature Sensor

REM

Remote